Bryant 313AAV Furnace Installation, Start-up, Operating And Service And Maintenance Instructions | Guidessimo.com (2024)

  • Page 1:

    Installation, Start--up, Operating and

    Ser v ic e and Mainte nanc e Inst r uc t ions

    Series 100/A

    313AAV/JAV PLUS 80X

    4--WAY MULTIPOISE

    INDUCED--COMBUSTION GAS FURNACE

    INPUT CAPACITI ES: 45,000 THRU 135,000 BTUH

    SAFETY CONSIDERATIONS 2........................

    INTRODUCTION 3..................................

    CODES AND STANDARDS 4..........................

    Safety 4........................................

    General Installation 5...............................

    Combustion and Ventilation Air 5.....................

    Duct Systems 5...................................

    Acoustical Lining and Fibrous Glass Duct 5.............

    Gas Piping and Gas Pipe Pressure Testing 5.............

    Electrical Connections 5............................

    Venting 5........................................

    ELECTROSTATIC DISCHARGE PRECAUTIONS

    PROCEDURE 5.....................................

    LOCATION 6.......................................

    INSTALLATION 10..................................

    Upflow Installation 10..............................

    Downflow Installation 11...........................

    Horizontal Installation 13...........................

    Filter Arrangement 14..............................

    Air Ducts 14.....................................

    Gas Piping 17....................................

    115 --V Wiring 22..................................

    START--UP, ADJUSTMENT, AND SAFETY CHECK 36.....

    General 36.......................................

    Start--up Procedures 36.............................

    Adjustments 36...................................

    Check Safety Controls 39...........................

    Checklist 40......................................

    SERVICE AND MAINTENANCE PROCEDURES 43.......

    Introduction 43...................................

    Care and Maintenance 46...........................

    Sequence of Operation 49...........................

    Wiring Diagrams 51...............................

    Troubleshooting 51................................

    ama

    REGISTERED

    ISO 9001:2000

    CERTIFIED

    NOTE: Read the entire instruction manual before starting the

    installation.

    Portions of the text and tables are reprinted from NFPA 54/ANSI

    Z223.1-- 2006E, with permission of National Fire Protection

    Association, Quincy, MA 02269 and American Gas Association,

    Washington DC 20001. This reprinted material is not the

    complete and official position of the NFPA or ANSI on the

    referenced subject, which is represented only by the standard in

    its entirety.

  • Page 2:

    2

    2-7/16"

    1-1/8"

    28-7/8"

    (733mm)

    25-1/4"

    22-9/16"

    JUNCTION BOX

    LOCATION

    7/8" DI A

    ACCESSORY

    1/2" (13 mm) DIA.

    THERMOSTAT WIRE ENTRY

    3-15/16" (84mm)

    LEFT HAND GAS

    ENTRY

    33-5/16"

    24-7/8"

    5-1/2"

    7/8" (22mm) DIA.

    ACCESSORY

    11/16"

    21-5/8"

    BOTTOM INLE T

    1-11/16"

    13/16"

    11/16"

    4-13/16"

    AIRFLOW

    19"

    OUTLE T

    13/16"

    11/16"

    8-9/16"

    VENT OUTLE T

    5 PLACES (TYP)

    3-3/4"

    1-3/4" DIA.RIGHT HAND

    GAS ENTRY

    7/8" DIA. K.O. WIRE ENTRY

    SIDE INLE T

    14-7/8"

    7/8" DIA. ACCESSORY

    1-1/4"

    1"

    22-1/16"

    A

    D

    F

    E

    (FLUE COLLAR)

    5-15/16"

    (135mm)

    24"

    CASING

    1-5/16"

    1/2" DIA. K.O.THERMOSTAT

    WIRE ENTRY

    ALTERNAT E

    JUNCTION BOX

    LOCATIONS (TYP)

    26-1/8"

    1-1/2"

    7-3/4"

    9-5/8"

    11-1/2"

    5-1/2"

    (664mm)

    (641mm)

    (573mm)

    (22mm)

    (846mm)

    (17mm)

    (549mm)

    (

    610mm

    )

    (43mm)

    (140mm)

    (632mm)

    (17mm)

    (140mm)

    (95mm)

    (21mm)

    (122mm)

    (217mm)

    (62mm)

    (33mm)

    (29mm)

    (483mm)

    (13mm)

    (44mm)

    (22mm)

    (22mm)

    (38mm)

    (560mm)

    (25mm)

    (32mm)

    (378mm)

    (17mm)

    (197mm)

    (244mm)

    (292mm)

    (21mm)

    A04037

    NOTES:

    1. Two additional 7/8---in. (22 mm) diameter holes are located in the top plate.

    2. Minimum return ---air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer’s recommendations for equivalent diameters.

    a. For 800 CFM---16---in. (406 mm) round or 14 1/2 x 12---in. (368 x 305 mm) rectangle.

    b. For 1200 CFM---20 ---in. (508 mm) roun d or 14 1/2 x 19 1/2 ---in. (368 x 495 mm) rectangle.

    c. For 1600 CFM---22 ---in. (559 mm) round or 14 1/2 x 22 1/16---in. (368 x 560mm) rectangle.

    d. For airflow requirements above 1800 C FM, see Air Delivery table in Product Da ta literature f or specif ic u se of single side inlets. T he use of both sideinlets,a

    combination of 1 side and the botto m, or the bottom only will ensur e adequate return air openings for airflow requirements above 1800 CFM.

    Fig. 1 -- Dimensional Drawing

    Table1–Dimensions

    FURNACE SIZE

    A

    CABINET

    WIDTH

    IN. (MM)

    D

    SUPPLY---AIR

    WIDTH

    IN. (MM)

    E

    RETURN---AIR

    WIDTH

    IN. (MM)

    F

    C.L. TOP AND

    BOTTOM FLUE

    COLLAR

    IN. (MM)

    FLUE

    COLLAR*

    IN. (MM)

    SHIP WT

    (LB / KG)

    FILTER

    MEDIA

    CABINET

    SIZE

    IN. (MM)

    045---08/024045 14---3/16 (360) 12---9/16 (319) 12---11/16 (322) 9---5/16 (237) 4 (102) 114 (52) 16 (406)

    070---16/048070 17---1/2 (445) 15---7/8 (403) 16 (406) 11---9/16 (294) 4 (102) 136 (62) 16 (406)

    090---16/048090 21 (533) 19---3/8 (492) 19--- 1/2 (495) 13--- 5/16 (338) 4 (102) 150 (68) 20 (508)

    110---20/060110 21 (533) 19---3/8 (492) 19--- 1/2 (495) 13--- 5/16 (338) 4 (102) 162 (73) 20 (508)

    135---20/060135 24---1/2 (622) 22---7/8 (581) 23 (584) 15---1/16 (383) 4 (102) 173 (78) 24 (610)

    * 5 in. or 6 in. (127 or 152 mm) vent connector may be required in some cases.

    SAFETY CONSIDERATIONS

    FIRE, EXPLOSION, ELECTRICAL SHOCK, AND

    CARBON MONOXIDE POISONING HAZARD

    Failure to follow this warning could result in dangerous

    operation, serious injury, death, or property damage.

    Improper installation, adjustment, alteration, service,

    maintenance, or use could cause carbon monoxide

    poisoning, explosion, fire, electrical shock, or other

    conditions which may cause personal injury or property

    damage. Consult a qualified service agency, local gas

    supplier, or your distributor or branch for information or

    assistance. The qualified service agency must use only

    factory--authorized and listed kits or accessories when

    modifying this product.

    !

    WARNING

    FURNACE RELIABILITY HAZARD

    Improper installation or misapplication of furnace may

    require excessive servicing or cause premature component

    failure.

    Application of this furnace should be indoors with special

    attention given to vent sizing and material, gas input rate,

    air temperature rise, unit leveling, and unit sizing.

    CAUTION

    !

    Improper installation, adjustment, alteration, service,

    maintenance, or use can cause explosion, fire, electrical shock, or

    other conditions which may cause death, personal injury, or

    property damage. Consult a qualified installer, service agency, or

    your distributor or branch for information or assistance. The

    qualified installer or agency must use factory -- authorized kits or

    accessories when modifying this product. Refer to the individual

    instructions packaged with the kits or accessories when installing.

    Follow all safety codes. Wear safety glasses, protective clothing,

    and work gloves. Have a fire extinguisher available. Read these

    313A

  • Page 3:

    3

    instructions thoroughly and follow all warnings or cautions

    include in literature and attached to the unit. Consult local

    building codes, the current editions of the National Fuel Gas

    Code (NFGC) NFPA 54/ANSI Z223.1 and the National

    Electrical Code (NEC) NFPA 70.

    In Canada, refer to the current editions of the National Standards

    of Canada CAN/CSA-- B149.1 and .2 Natural Gas and Propane

    Installation Codes, and Canadian Electrical Code CSA C22.1

    Recognize safety information. This is the safety --alert symbol

    .

    When you see this symbol on the unit and in instructions or

    manuals, be alert to the potential for personal injury.

    Understand the signal words DANGER, WARNING,and

    CAUTION. These words are used with the s afety--alert symbol.

    DANGER identifies the most serious hazards which will result in

    severe personal injury or death. WARNING signifies hazards

    which could result in personal injury or death. CAUTION is

    used to identify unsafe practices which may result in minor

    personal injury or product and property damage. NOTE is used

    to highlight suggestions which will result in enhanced

    installation, reliability, or operation.

    CUT HAZARD

    Failure to follow this caution may result in personal injury .

    Sheet metal parts may have sharp edges or burrs. Use care

    and wear appropriate protective clothing, safety glasses and

    gloves when handling parts and servicing furnaces.

    CAUTION

    !

    1. Use only with type of gas approved for this furnace. Refer

    to the furnace rating plate.

    2. Install this furnace only in a location and position as

    specified in the “Location” section of these instructions.

    3. Provide adequate combustion and ventilation air to the

    furnace space as specified in “Air for Combustion and

    Ventilation” section.

    4. Combustion products must be discharged outdoors.

    Connect this furnace to an approved vent system only, as

    specified inthe “Venting” section of these instructions.

    5. Never test for gas leaks with an open flame. Use a

    commercially available soap solution made specifically for

    the detection of leaks to check all connections, as specified

    in the “Gas Piping” section.

    6. Always install furnace to operate within the furnace’s

    intended temperature--rise range with a duct system which

    has an external static pressure within the allowable range,

    as specified in the “Start--Up, Adjustments, and Safety

    Check” section. See furnace rating plate.

    7. When a furnace is installed so that supply ducts carry air

    circulated by the furnace to areas outside the space

    containing the furnace, the return air shall also be handled

    by duct(s) sealed to the furnace casing and terminating

    outside the space containing the furnace. See “Air Ducts”

    section.

    8. A gas--fired furnace for installation in a residential garage

    must be installed as specified in the warning box in the

    “Location” section.

    9. The furnace may be used for construction heat provided

    that the furnace installation and operation complies with

    the first CAUTION in the LOCATION section of these

    instructions.

    10. These Multipoise Gas--Fired Furnaces are CSA (formerly

    A.G.A. and C.G.A). design-- certified for use with natural

    and propane gases (see furnace rating plate) and for

    installation in alcoves, attics, basem*nts, closets, utility

    rooms, crawlspaces, and garages. The furnace is

    factory-- shipped for use with natural gas. A CSA listed

    accessory gas conversion kit is required to convert furnace

    for use with propane gas.

    11. See Fig. 2 for required clearances to combustible

    construction.

    12. Maintain a 1--in. (25 mm) clearance from combustible

    materials to supply air ductwork for a distance of 36

    inches (914 mm) horizontally from the furnace. See NFPA

    90B or local code for further requirements.

    13. These furnaces SHALL NOT be installed directly on

    carpeting, tile, or any other combustible material other

    than wood flooring. In downflow installations, factory

    accessory floor base MUST be used when installed on

    combustible materials and wood flooring. Special base is

    not required when this furnace is installed on

    manufacturer’s Coil Assembly Part No. CAR, CAP,

    CNRV, and CNPV, o r when Coil Box Part No. KCAKC is

    used. See Fig. 2 for clearance to combustible construction

    information.

    INTRODUCTION

    Series 100/A 4--way multipoise Category I fan--assisted furnace is

    CSA design--certified. A Category I fan--assisted furnace is an

    appliance equipped with an integral mechanical means to either

    draw or force products of combustion through the combustion

    chamber and/or heat exchanger. The furnace is factory-- shipped

    for use with natural gas.

    This furnace is not approved for installation in mobile homes,

    recreational vehicles, or outdoors. This furnace is designed for

    minimum continuous return-- air temperature of 60_F(16_C)db

    or intermittent operation down to 55_F(13_C) db such as when

    used with a night setback thermostat. Return--air temperature

    must not exceed 85_F(29_C) db. Failure to follow these

    return--air temperature limits may affect reliability of heat

    exchangers, motors, and controls. (See Fig. 3).

    For accessory installation details, refer to the applicable

    instruction literature.

    NOTE: Remove all shipping brackets and materials before

    operating the furnace.

    313A

  • Page 4:

    4

    A08471

    Fig. 2 -- Clearances to Combustibles

    CODES AND STANDARDS

    Follow all national and local codes and standards in addition to

    these instructions. The installation must comply with regulations

    of the serving gas supplier, local building, heating, plumbing, and

    other codes. In absence of local codes, the installation must

    comply with the national codes listed below and all authorities

    having jurisdiction.

    In the United States and Canada, follow all codes and standards

    for the following:

    Safety

    S USA: National Fuel Gas Code (NFGC) NFPA

    54 -- 2006/ANSI Z223.1--2006 and the Installation Stan-

    dards, Warm Air Heating and Air Conditioning Sys-

    tems ANSI/NFPA 90B

    S CANADA: CSA B149.1--05 National Standard of

    Canada Natural Gas and Propane Installation Codes

    (CAN/CSA--B149.1 --05)

    313A

  • Page 5:

    5

    Min 60ºF / 16ºC

    Max 85ºF/ 29ºC

    A02055

    Fig. 3 -- Return Air Temperature

    General

    Installation

    S US: Current edition of the NFGC and the NFPA 90B.

    For copies, contact the National Fire Protection

    Association Inc., Batterymarch Park, Quincy , MA

    02269; (www.NFPA.org) or for only the NFGC,

    contact the American Gas Association, 400 N. Capitol

    Street, N.W., Washington, DC 20001 (www.AGA.org).

    S CANADA: CAN/CSA--B149.1 --05. For a copy,

    contact Standard Sales, CSA International, 178

    Rexdale Boulev ard, Etobico*ke (Toronto), Ontario,

    M9W 1R3 Canada.

    Combustion and Ventilation

    Air

    S US: NGFC NFPA54/ANSI Z223.1--2006 Section 9.3,

    Air for Combustion and Ventilation.

    S CANADA: Part 8 of CAN/CSA--B149.1--05, Venting

    Systems and Air Supply for Appliances.

    Duct

    Systems

    S US and CANADA: Air Conditioning Contractors

    Association (ACCA) Manual D, Sheet Metal and Air

    Conditioning Contractors National Asso ciation

    (SMACNA), or American Society of Heating,

    Refrigeration, and Air Conditioning Engineers

    (ASHRAE) 2005 Fundamentals Handbook Chapter 35

    or 2004 HVAC Systems and Equipment Handbook

    Chapters 9 and 16.

    Acoustical Lining and Fibrous Glass

    Duct

    S US and CANADA: current edition of SMACNA and

    NFPA 90B as tested by UL Standard 181 for Class I

    Rigid Air Ducts

    Gas Piping and Gas Pipe Pressure T

    esting

    S US: NFGC NFPA54/ANSI Z223.1-- 2006; chapters 5,

    6, 7, and 8 and National Plumbing Codes.

    S CANADA: CAN/CSA--B149.1 --05 Parts 4, 5, and 6

    Appendices A, B, E, and H.

    Electrical

    Connections

    S US: National Electrical Code (NEC) ANSI/NFPA

    70 -- 2008.

    S CANADA: Canadian Electrical Code CSA C22.1.

    V

    enting

    S US: NFGC NFPA 54 / ANSI Z223.1-- 2006; Chapters

    12 and 13.

    S CANADA: CAN/CSA--B149.1--05 Part 8 and

    Appendix C.

    ELECTROSTATIC DISCHARGE (ESD)

    PRECAUTIONS PROCEDURE

    FURNACE RELIABILITY HAZARD

    Improper installation or service of furnace may cause

    premature furnace component failure.

    Electrostatic discharge can affect electronic components.

    Follow the Electrostatic Dischar ge Precautions Procedure

    listed below during furnace installation and servicing to

    protect the furnace electronic control. Precautions will

    prevent electrostatic discharges from personnel and hand

    tools which are held during the procedure. These

    precautions will help to avoid exposing the control to

    electrostatic discharge by putting the furnace, the control,

    and the person at the same electrostatic potential.

    CAUTION

    !

    1. Disconnect all power to the furnace. Multiple disconnects

    maybe req u ired. DO NOT TOUCH THE CONTROL OR

    ANY WIRE CONNECTED TO THE CONTROL PRIOR

    TO DISCHARGING YOUR BODY’S

    ELECTROSTATIC CHARGE TO GROUND.

    2. Firmly touch the clean, unpainted, metal surface of the

    furnace chassis which is close to the control. Firmly touch

    the clean, unpainted, metal surface of the furnace chassis

    which is close to the control. Tools held in a person’s hand

    during grounding will be satisfactorily discharged.

    3. After touching the chassis, you may proceed to service the

    control or connecting wires as long as you do nothing to

    recharge your body with static electricity (for example;

    DO NOT move or shuffle your feet, do not touch

    ungrounded objects, etc.).

    4. If you touch ungrounded objects (and recharge your body

    with static electricity), firmly touch a clean, unpainted

    metal surface of the furnace again before touching control

    or wires.

    5. Use this procedure for installed and uninstalled

    (ungrounded) furnaces.

    313A

  • Page 6:

    6

    THE BLOWER IS LOCATED

    TO THE RIGHT OF THE

    BURNER SECTION, AND

    AIR CONDITIONED AIR IS

    DISCHARGED TO THE LEFT.

    THE BLOWER IS

    LOCATED BELOW THE

    BURNER SECTION, AND

    CONDITIONED AIR IS

    DISCHARGED UPWARD.

    THE BLOWER IS

    LOCATED ABOVE THE

    BURNER SECTION, AND

    CONDITIONED AIR IS

    DISCHARGED DOWNWARD

    THE BLOWER IS

    LOCATED TO THE LEFT

    OF THE BURNER SECTION,

    AND CONDITIONED AIR IS

    DISCHARGED TO THE RIGHT.

    A02097

    Fig. 4 -- Multipoise Orientations

    6. Before removing a new control from its container,

    discharge your body’s electrostatic charge to ground to

    protect the control from damage. If the control is to be

    installed in a furnace, follow items 1 through 4 before

    bringing the control or yourself in contact with the

    furnace. Put all used and new controls into containers

    before touching ungrounded objects.

    7. An ESD service kit (available from commercial sources)

    mayalsobeusedtopreventESDdamage.

    LOCATION

    GENERAL

    This multipoise furnace is shipped in packaged configuration.

    Some assembly and modifications are required when used in any

    of the four applications shown in Fig. 4.

    This furnace must:

    S be installed so the electrical components are protected

    from water.

    S not be installed directly on any combustible material

    other than wood flooring (refer to SAFETY

    CONSIDERATIONS).

    S be located as close to the chimney or vent and attached

    to an airdistribution system. Refer to Air Ducts section.

    S be provided ample space for servicing and cleaning.

    Always comply with minimum fire protection

    clearances shown on the furnace clearance to

    combustible label.

    The following types of furnace installations may require

    OUTDOOR AIR for combustion due to chemical exposures:

    S Commercial buildings

    S Buildings with indoor pools

    S Laundry rooms

    S Hobby or craft rooms, and

    S Chemical storage areas

    CARBON MONOXIDE POISONING HAZARD

    Failure to follow this warning could result in personal

    injury or death, and unit component damage.

    Corrosive or contaminated air may cause failure of parts

    containing flue gas, which could leak into the living space.

    Air for combustion must not be contaminated by halogen

    compounds, which include fluoride, chloride, bromide, and

    iodide. These elements can corrode heat exchangers and

    shorten furnace life. Air contaminants are found in aerosol

    sprays, detergents, bleaches, cleaning solvents, salts, air

    fresheners, and other household products. Do not install

    furnace in a corrosive or contaminated atmosphere. Make

    sure all combustion and circulating air requirements are met,

    in addition to all local codes and ordinances.

    !

    WARNING

    If air is exposed to the following substances, it should not be used

    for combustion air, and outdoor air may be required for

    combustion:

    S Permanent wave solutions

    S Chlorinated waxes and cleaners

    S Chlorine based swimming pool chemicals

    S Wate softening chemicals

    S De--icing salts or chemicals

    S Carbon tetrachloride

    S Haloge type refrigerants

    S Cleaning solvents (such as perchloroethylene)

    S Printing inks, paint removers, varnishes, etc.

    S Hydrochloric acid

    S Cements and glues

    S Antistatic fabric softeners for clothes dryers

    313A

  • Page 7:

    7

    S Masonry acid washing materials

    All fuel --burning equipment must be supplied with air for fuel

    combustion. Sufficient air must be provided to avoid negative

    pressure in the equipment room or space. A positive seal must be

    made between the furnace cabinet and the return--air duct to

    prevent pulling a ir from the burner area and from draft safeguard

    opening.

    18-IN. (457.2 mm)

    MINIMUM TO BURNERS

    A93044

    Fig. 5 -- Installation in a Garage

    ELECTRICAL OPERATION HAZARD

    Failure to follow this warning could result in personal

    injury, death, and/or property damage.

    When the furnace is installed in a residential garage, the

    burners and ignition sources must be located at least 18

    inches above the floor. The furnace must be located or

    protected to avoid damage by vehicles. When the furnace is

    installed in a public garage, airplane hangar, or other

    building having a hazardous atmosphere, the furnace must

    be installed in accordance with the NFGC or

    CAN/CSA--B149.1--05. (See Fig. 5).

    !

    WARNING

    PERSONAL INJURY AND/OR PROPERTY

    DAMAGE HAZARD

    Improper use or installation of this furnace may cause

    premature furnace component failure.

    This gas furnace may be used for heating buildings under

    construction provided that:

    --The furnace is permanently installed with all electrical

    wiring, piping, venting and ducting installed according to

    these installation instructions. A return air duct is provided,

    sealed to the furnace casing, and terminated outside the

    space containing the furnace. This prevents a negative

    pressure condition a s created by the circulating air blower,

    causing a flame rollout and/or drawing combustion

    products into the structure.

    -- The furnace is controlled by a thermostat. It may not be

    “hot wired” to provide heat continuously to the structure

    without thermostatic control.

    -- Clean outside air is provided for combustion. This is to

    minimize the corrosive effects of adhesives, sealers and

    other construction materials. It also prevents the

    entrainment of drywall dust into combustion air, which can

    cause fouling and plugging of furnace components.

    --The temperature of the return air to the furnace is

    maintained between 55_F(13_C) and 80_F(27_C), with

    no evening setback or shutdown. The use of the furnace

    while the structure is under construction is deemed to be

    intermittent operation per our installation instructions.

    --The air temperature rise is within the rated rise range on

    the furnace rating plate, and the gas input rate has been set

    to the nameplate value.

    --The filters used to clean the circulating air during the

    construction process must be either changed or thoroughly

    cleaned prior to occupancy .

    --The furnace, ductwork and filters are cleaned as necessary

    to remove drywall dust and construction debris from all

    HVAC system components after construction is completed.

    -- Verify proper furnace operating conditions including

    ignition, gas input rate, air temperature rise, and venting

    according to these installation instructions.

    CAUTION

    !

    Table 2 – Minimum Free Area Required for Each Combustion Air Opening or Duct to Outdoors

    FUR-

    NACE

    INPUT

    (BTUH)

    TWO HORIZONTAL DUCTS

    (1 SQ. IN./2,000 BTUH)

    (1,100 SQ. MM/KW)

    SINGLE DUCT OR OPENING

    (1 SQ. IN./3,000 BTUH)

    (734 SQ. MM/KW)

    TWO OPENINGS OR VERTICAL

    DUCTS

    (1 SQ. IN./4,000 BTUH)

    (550 SQ. MM/KW)

    Free Area of Opening

    and Duct

    (sq.in./sq.mm)

    Round Duct

    Diameter

    (in./mm)

    Free Area of Open-

    ing and Duct

    (sq.In./sq.mm)

    Round Duct

    Diameter

    (in. / mm)

    Free Area of

    Opening and Duct

    (sq.In./sq.mm)

    Round Duct

    Diameter

    (In./mm)

    44,000 22 (14193) 6 (152) 14.7 (9484) 5 (127) 11 (7097) 4 (102)

    66,000 33 (21290) 7 (178) 22 (14193) 6 (152) 16.5 (10645) 5 (127)

    88,000 44 (28387) 8 (203) 29.3 (18903) 7 (178) 22 (14193) 6 (152)

    110,000 55 (35484) 9 (229) 36.7 (23677) 7 (178) 27.5 (17742) 6 (152)

    132,000 66 (42581) 10 (254) 44 (28387) 8 (203) 33 (21290) 7 (178)

    EXAMPLES: Determining Free Area

    FURNACE WATER HEATER TOTAL INPUT

    110,000 + 30,000 = (140,000 divided by 4,000) = 35.0 Sq. In. for each two Verti cal Ducts or Openings

    66,000 + 40,000 = (106,000 divided by 3,000) = 35.3 Sq. In. for a Single Duct or Opening

    88,000 + 30,000 = (118,000 divided by 2,000) = 59.0 Sq. In. for each of two Horizontal Ducts

    313A

  • Page 8:

    8

    Table 3 – Minimum Space volumes for 100% combustion, Ventilation, and Dilution from Indoors

    ACH*

    OTHER THAN FAN---AS SISTED TOTAL

    (1,000’S BTUH GAS INPUT RATE

    FAN---ASSISTED TOTAL

    (1,000’S BTUH GAS INPUT RATE)

    30 40 50 44 66 88 110 132

    SpaceVolume(ft.

    3

    )

    0.60 1,050 1,400 1,750 1,100 1,650 2,200 2,750 3,300

    0.50 1,260 1,680 2,100 1,320 1,980 2,640 3,300 3,960

    0.40 1,575 2,100 2,625 1,650 2,475 3,300 4,125 4,950

    0.30 2,100 2,800 3,500 2,200 3,300 4,400 5,500 6,600

    0.20 3,150 4,200 5,250 3,300 4,950 6,600 8,250 9,900

    0.10 6,300 8,400 10,500 6,600 9,900 13,200 16,500 19,800

    0.00 NP NP NP NP NP NP NP NP

    *Air Changes/Hour

    FIRE HAZARD

    Failure to follow this warning could result in personal

    injury, death and/or property damage.

    Do not install the furnace on its back or hang furnace with

    control compartment facing downward. Safety control

    operation will be adversely affected. Never connect

    return--air ducts to the back of the furnace. (See Fig. 6.)

    !

    WARNING

    A02054

    Fig. 6 -- Prohibit Installation on Back

    FURNACE CORROSION HAZARD

    Failure to follow this caution may result in furnace damage.

    Air for combustion must not be contaminated by halogen

    compounds, which include fluoride, chloride, bromide, and

    iodide. These elements can corrode heat exchangers and

    shorten furnace life. Air contaminants are found in aerosol

    sprays, detergents, bleaches, cleaning solvents, salts, air

    fresheners, and other household products.

    CAUTION

    !

    LOCATION RELATIVE TO COOLING EQUIPMENT

    The cooling coil must be installed parallel with, or on the

    downstream side of the unit to avoid condensation in the heat

    exchangers. When installed parallel with the furnace, dampers or

    other flow control must prevent chilled air from entering the

    furnace. If the dampers are manually operated, they must be

    equipped with means to prevent operation of either unit unless

    the damper is in the full--heat or full --cool position.

    AIR FOR COMBUSTION AND

    VENTILATION

    Provisions for adequate combustion, ventilation, and dilution air

    must be provided in accordance with:

    S U.S. installations: Section 9.3 of the NFGC

    NFPA54/ANSI Z223.1 --2006, Air for Combustion and

    Ventilation, and applicable provisions of the local

    building codes.

    !

    WARNING

    CARBON MONOXIDE POISONING HAZARD

    Failure to follow this warning could result in personal injury

    or death.

    The operation of exhaust fans, kitchen ventilation fans,

    clothes dryers, attic exhaust fans or fireplaces could create a

    NEGATIVE PRESSURE CONDITION at the furnace.

    Make--up air MUST be provided for the ventilation devices,

    in addition to that required by the furnace. Refer to Carbon

    Monoxide Poisoning Hazard warning in venting section of

    these instructions to determine if an adequate amount of

    make--up air is available.

    S Canadian installations: Part 8 of th e

    CAN/CSA--B149.1--05, Venting Systems and Air

    Supply for Appliances, and all authorities having

    jurisdiction.

    The requirements for combustion and ventilation air depend upon

    whether or not the furnace is located in a space having a volume

    of at least 50 cubic feet per 1,000 Btuh input rating for all g as

    appliances installed in the space.

    S Spaces having less than 50 cubic feet per 1,000 Btuh

    require the OUTDOOR COMBUSTION AIR

    METHOD.

    S Spaces having at least 50 cubic feet per 1,000 Btuh

    may use the INDOOR COMBUSTION AIR,

    STANDARD o r KNOWN AIR INFILTRATION

    METHOD.

    Outdoor Combustion Air

    Method

    1. Provide the space with sufficient air for proper

    combustion, ventilation, and dilution of flue gases using

    permanent horizontal or vertical duct(s) or opening(s)

    directly communicating with the outdoors or spaces that

    freely communicate with the outdoors.

    2. Fig. 7 illustrates how to provide TWO OUTDOOR

    OPENINGS, one inlet and one outlet combustion and

    ventilation airopening, to the outdoors.

    313A

  • Page 9:

    9

    a. One opening MUST commence within 12--in. (300 mm)

    of the ceiling and the second opening MUST commence

    within 12--in. (300 mm) of the floor .

    b. Size openings and ducts per Fig. 7 and Table 2.

    c. TWO HORIZONTAL DUCTS require 1 square inch of

    free area per 2,000 Btuh (1,100 mm

    2

    /kW) of combined

    input for all gas appliances in the space per Fig. 7 and

    Table 2.

    d. TWO OPENINGS OR VERTICAL DUCTS require 1

    square inch of free area per 4,000 Btuh (550 mm

    2

    /kW)

    for combined input of all gas appliances in the space per

    Fig. 7 and Table 2.

    3. ONE OUTDOOR OPENING requires:

    a. 1 square inch of free area per 3,000 Btuh (734 mm

    2

    /kW)

    for combined input of all gas appliances in the space per

    Table 2 and

    b. Not less than the sum of the areas of all vent connectors

    in the space.

    The opening shall commence within 12” (300 mm) of the ceiling.

    Appliances in the space shall have clearances of at least 1” (25

    mm) from the sides and back and 6” (150 mm) from the front.

    The opening shall directly communicate with the outdoors or

    shall communicate through a vertical or horizontal duct to the

    outdoors or spaces (crawl or attic) that freely communicate with

    the outdoors.

    1 SQ IN .

    PER

    4000

    BTUH*

    DUCTS

    TO

    O UTDOORS

    1 SQ IN.

    PER 4000

    BTUH*

    C IRCULA TING

    AIR DUCTS

    VENT

    THR OUGH

    R OOF

    D

    B

    A

    C

    E

    1 SQ IN.

    PER 4000

    BTUH*

    DUCT

    TO

    OUTDOORS

    CIRCULA TING AIR DUCT S

    1 SQ IN.

    PER 2000

    BTUH*

    1 SQ IN.

    PER 2000

    BTUH*

    DUCT S

    TO

    OUTDOORS

    12 ″ MAX

    12 ″ MAX

    12 ″ MAX

    12 ″

    MAX

    12 ″

    MAX

    OUTDOORS

    1 SQ IN .

    PER

    4000

    BTUH*

    F

    G

    CLEARANCE IN FRONT

    OF COMB USTION AIR

    OPENINGS SHALL BE

    AT LEAST 3 IN .

    (305mm)

    (305mm)

    (305mm)

    (305mm)

    (305mm)

    (76mm)

    *Minimum dimensions of 3 in. (76 mm).

    NOTE: Use any of the following combinations of openings:

    A&B, C&D, D&E, F&G

    A03174

    Fig. 7 -- Air fo r Combustion, Ventilation, and Dilution from

    Outdoors

    Indoor Combustion Air -- NFPA & AGA

    Standard and Known-- Air-- Infiltration Rate Methods

    Indoor air is permitted for combustion, ventilation, and dilution,

    if the Standard or Known--Air--Infiltration Method is used.

    CARBON MONOXIDE POISONING HAZARD

    Failure to follow this warning could result in death and/or

    personal injury.

    Many homes require air to be supplied from outdoors for

    furnace combustion, ventilation, and dilution of flue gases.

    The furnace combustion air supply must be provided in

    accordance with this instruction manual.

    !

    WARNING

    The Standard Method:

    1. The space has no less volume than 50 cubic feet per 1 ,000

    Btuh of the maximum input ratings for all gas appliances

    installed in the space and

    2. The air infiltration rate is not known to be less than 0.40

    air changes per hour (ACH).

    The Known Air Infiltration Rate Method shall be used, if the

    infiltration rate is known to be:

    1. Less than 0.40 ACH and

    2. Equal to or greater than 0.10 ACH

    Infiltration rates greater than 0.60 ACH shall not be used. The

    minimum required volume of the space varies with the number of

    ACH and shall be determined per Table 3 or Equations 1 and 2.

    Determine the minimum required volume for each appliance in

    the space and add the volumes together to get the total minimum

    required volume for the space.

    Table 3--Minimum Space Volumes were determined by using

    the following equations from the National Fuel Gas Code ANSI

    Z223.1-- 2006/NFPA 54 --2006, 9.3.2.2:

    1. For other than fan-- assisted appliances, such as a draft

    hood -- equipped water heater:

    Volume

    Other

    =

    21ft

    3

    ACH

    I

    other

    1000 Btu/hr

    A04002

    2. For fan--assisted appliances such as this furnace:

    Volume

    Fan

    =

    15ft

    3

    ACH

    I

    fan

    1000 Btu/hr

    A004003

    If:

    Iother = combined input of all other than fan-- assisted appliances

    in Btuh/hr

    Ifan = combined input of all fan --assisted appliances in Btuh/hr

    ACH = air changes per hour (ACH shall not exceed 0.60.)

    The following requirements apply to the Standard Method and to

    the Known Air Infiltration Rate Method.

    1. Adjoining rooms can be considered part of a space if:

    a. There are no closable doors between rooms.

    b. Combining spaces on same floor level. Each opening

    shall have free area of at least 1 in.

    2

    /1,000 Btuh (2,000

    mm

    2

    /kW) of the total input rating of all gas appliances

    in the space, but not less than 100 in.

    2

    (0.06 m

    2

    ). One

    opening shall commence within 12” (300 mm) of the

    ceiling and the second opening shall commence within

    12” (300 mm) of the floor. The minimum dimension of

    air openings shall be at least 3 in. (80 mm). (See Fig. 8.)

    c. Combining space on different floor levels. The volumes

    of spaces on different floor levels shall be considered as

    communicating spaces if connected by one or more

    permanent openings in doors or floors having free area

    313A

  • Page 10:

    10

    of at least 2 in.

    2

    /1,000 Btuh (4,400 mm

    2

    /kW) of total

    input rating of all gas appliances.

    2. An attic or crawlspace may be considered a space that

    freely communicates with the outdoors provided there are

    adequate permanent ventilation openings directly to

    outdoors having free area of at least 1 --in.

    2

    /4,000 Btuh of

    total input rating forall gas appliances in the space.

    3. In spaces that use the Indoor Combustion Air Method,

    infiltration should be adequate to provide air for

    combustion, permanent ventilation and dilution of flue

    gases. However, in buildings with unusually tight

    construction, additional air MUST be provided using the

    methods described in the Outdoor Combustion Air

    Method section.

    Unusually tight construction is defined as construction with:

    a. Walls and ceilings exposed to the outdoors have a

    continuous, sealed vapor barrier. Openings are gasketed

    or sealed and

    CIRCULATING AIR

    DUCTS

    6" MIN

    (FRONT)

    Ü

    CIRCULATING AIR DUCTS

    VENT THROUGH ROOF

    1 SQ IN.

    PER 1000

    BTUH* IN DOOR

    OR WALL

    12" MAX

    1 SQ IN.

    PER 1000

    BTUH* IN DOOR

    OR WALL

    12" MA X

    UNCONFINED

    SPACE

    INTERIOR

    HEATED

    SPACE

    CLEARANCE IN FRONT OF COMBUSTION AIR

    OPENINGS SHALL BE AT LEAST 3 IN.

    (305mm)

    (152mm)

    (305mm)

    *Minimum opening size is 100 in.

    2

    with minimum dimen sions of 3 in. ( 76

    mm).

    *Minimum of 3 in. (76 mm), when type ---B1 vent is used.

    A03175

    Fig. 8 -- Air fo r Combustion, Ventilation, and Dilution from

    Indoors

    b. Doors and openable windows are weatherstripped and

    c. Other openings are caulked or sealed. These include

    joints around window and door frames, between sole

    plates and floors, between wall--ceiling joints, between

    wall panels, at penetrations for plumbing, electrical and

    gas lines, etc.

    Combination of Indoor and Outdoor

    Air

    1. Indoor openings shall comply with the Indoor

    Combustion Air Method below and,

    2. Outdoor openings shall be located as required in the

    Outdoor Combustion Air Method menioned previously

    and,

    3. Outdoor openings shall be sized as follows:

    a. Calculate the Ratio of all Indoor Space volume divided

    by required volume for Indoor Combustion Air

    Method below.

    A02098

    Fig. 9 -- Removing Bottom Closure Panel

    b. Outdoor opening size reduction Factor is 1 minus the

    Ratio in a. above.

    c. Minimum size of Outdoor openings shall be the size

    required in Outdoor Combustion Air Method above

    multiplied by reduction Factor in b. above. The minimum

    dimension of air openings shall be not less than 3 in. (80

    mm).

    INSTALLATION

    UPFLOW INSTALLATION

    Bottom Return Air Inlet

    These furnaces are shipped with bottom closure panel installed in

    bottom return-- air opening. Remove and discard this panel when

    bottom return air is used. To remove bottom closure panel,

    perform the following:

    1. Tilt or raise furnace and remove two screws holding

    bottom filler panel. (See Fig. 9.)

    2. Rotate bottom filler panel downward to release holding

    tabs.

    3. Remove bottom closure panel.

    4. Reinstall bottom filler panel and screws.

    Side Return Air

    Inlet

    These furnaces are shipped with bottom closure panel installed in

    bottom return-- air opening. This panel MUST be in place when

    only side return air is used.

    NOTE: Side return-- air openings can be used in UPFLOW and

    most HORIZONTAL configurations. Do not use side return-- air

    openings in DOWNFLOW configuration.

    Leveling Legs (If Desir

    ed)

    In upflow position with side return inlet(s), leveling legs may be

    used. (See Fig. 10.) Install field--supplied, 5/16 x 1-- 1/2 in. (8 x

    38 mm) (max) corrosion--resistant machine bolts, washers and

    nuts.

    NOTE: Bottom closure must be used when leveling legs are

    used. It may be necessary to remove and reinstall bottom closure

    panel to install leveling legs. To remove bottom closure panel, see

    Item 1. in Bottom Return Air Inlet section.

    To install leveling legs:

    1. Position furnace on its back. Locate and drill a hole in

    each bottom corner of furnace. (See Fig. 10.)

    2. For each leg, install nut on bolt and then install bolt and

    nut in hole. (Install flat washer if desired.)

    3. Install another nut on other side of furnace base. (Install

    flat washer if desired.)

    313A

  • Page 11:

    11

    1

    3

    /

    4

    1

    3

    /

    4

    1

    3/

    4

    1

    3/

    4

    5/

    16

    5

    /

    16

    5/

    16

    5/

    16

    (44mm)

    (8mm)

    (44mm)

    (8mm)

    (8mm)

    (8mm)

    (44mm)

    (44mm)

    A89014

    Fig. 10 -- Leveling Legs

    4. Adjust outside nut to provide desired height, and tighten

    inside nut to secure arrangement.

    5. Reinstall bottom closure panel if removed.

    DOWNFLOW INSTALLA

    TION

    NOTE: For downflow applications, this furnace is approved for

    use on combustible flooring when any one of the following 3

    accessories are used:

    S Special Base, KGASB

    S Cased Coil Assembly Part No. CNPV, CNRV, CAP, or

    CAR

    S Coil Box Part No. KCAKC

    1. Determine application being installed from Table 4.

    2. Construct hole in floor per Table 4 and Fig. 11.

    3. Construct plenum to dimensions specified in Table 4 and

    Fig. 11.

    4. If downflo w subbase, KGASB is used, install as shown in

    Fig. 12. If Coil Assembly Part No. CNPV, CNRV, CAP

    and CNR or Coil Box PartNo. KCAKC is used, install as

    shown in Fig. 13.

    NOTE: It is recommended that the perforated supply-- air duct

    flanges be completely folded over or removed from furnace when

    installing the furnace on a factory--supplied cased coil or coil box.

    To remove the supply-- air duct flange, use wide duct pliers or

    hand seamers to bend flange back and forth until it breaks off. Be

    careful of sharp edges. (See Fig. 14.)

    Bottom Return Air

    Inlet

    These furnaces are shipped with bottom closure panel installed in

    bottom return-- air opening. Remove and discard this panel when

    bottom return air is used. To remove bottom closure panel,

    perform the following:

    1. Tilt or raise furnace and remove two screws holding

    bottom filler panel. (See Fig. 9.)

    2. Rotate bottom filler panel downward to release holding

    tabs.

    3. Remove bottom closure panel.

    4. Reinstall bottom filler panel and screws

    PLENUM

    OPENING

    C

    A

    B

    D

    FLOOR

    OPENING

    A96283

    Fig. 11 -- Floor and Plenum Opening Dimensions

    DOWNFLOW

    SUBBASE

    SHEET METAL

    PLENUM

    FLOOR

    OPENING

    FURNACE

    (OR COIL CASING

    WHEN USED)

    COMBUSTIBLE

    FLOORING

    A96285

    Fig. 12 -- Furnace, Plenum, and Subbase Installed

    on a Combustible Floor

    313A

  • Page 12:

    12

    APPROVED

    COIL ASSEMBLY

    OR

    COIL BOX

    FURNACE

    SHEET METAL

    PLENUM

    FLOOR

    OPENING

    COMBUSTIBLE

    FLOORING

    A08556

    Fig. 13 -- Furnace, Plenum, and Coil Assembly or

    Coil Box Installed on a Combustible Floor

    313A

  • Page 13:

    13

    Table 4 – Opening Dimensions -- In. (mm)

    FURNACE

    CASING

    WIDTH

    APPLICATION

    PLENUM OPENING FLOOR OPENING

    A B C D

    14–3/16

    (360)

    Upflow Applications on Combustible or Noncombustible Floor-

    ing (KGASB subbase not required)

    12---11/16

    (322)

    21---5/8

    (549)

    13---5/16

    (338)

    22---1/4

    (565)

    Downflow Applications on Noncombustible Flooring (KGASB

    subbase not required)

    12---9/16

    (319)

    19

    (483)

    13---3/16

    (335)

    19---5/8

    (498)

    Downflow applications on combustible flooring (KGASB sub-

    base required)

    11---13/16

    (284)

    19

    (483)

    13---7/16

    (341)

    20---5/8

    (600)

    Downflow Applications on Combustible Flooring with CNPV,

    CNRV, CAR, or CAP Coil Assembly or KCAKC coil box

    (KGASB subbase not required)

    12---5/16

    (313)

    19

    (483)

    13---5/16

    (338)

    20

    (508)

    17–1/2

    (445)

    Upflow Applications on Combustible or Noncombustible Floor-

    ing (KGASB subbase not required)

    16

    (406)

    21---5/8

    (549)

    16---5/8

    (422)

    22---1/4

    (565)

    Downflow Applications on Noncombustible Flooring (KGASB

    subbase not required)

    15---7/8

    (403)

    19

    (483)

    16---1/2

    (419)

    19---5/8

    (498)

    Downflow applications on combustible flooring (KGASB sub-

    base required)

    15---1/8

    (384)

    19

    (483)

    16---3/4

    (425)

    20---5/8

    (600)

    Downflow Applications on Combustible Flooring with CNPV,

    CNRV, CAR, or CAP Coil Assembly or KCAKC coil box

    (KGASB subbase not required)

    15---1/2

    (394)

    19

    (483)

    16---1/2

    (419)

    20

    (508)

    21

    (533)

    Upflow Applications on Combustible or Noncombustible Floor-

    ing (KGASB subbase not required)

    19---1/2

    (495)

    21---5/8

    (549)

    20---1/8

    (511)

    22---1/4

    (565)

    Downflow Applications on Noncombustible Flooring (KGASB

    subbase not required)

    19---3/8

    (492)

    19

    (483)

    20

    (508)

    19---5/8

    (498)

    Downflow applications on combustible flooring (KGASB sub-

    base required)

    18---5/8

    (473)

    19

    (483)

    20---1/4

    (514)

    20---5/8

    (600)

    Downflow Applications on Combustible Flooring with CNPV,

    CNRV, CAR, or CAP Coil Assembly or KCAKC coil box

    (KGASB subbase not required)

    19

    (483)

    19

    (483)

    20

    (508)

    20

    (508)

    24---1/2

    (622)

    Upflow Applications on Combustible or Noncombustible Floor-

    ing (KGASB subbase not required)

    23

    (584)

    21---1/8

    (537)

    23---5/8

    (600)

    22---1/4

    (565)

    Downflow Applications on Noncombustible Flooring (KGASB

    subbase not required)

    22---7/8

    (581)

    19

    (483)

    23---1/2

    (597)

    19---5/8

    (498)

    Downflow applications on Combustible flooring (KGASB sub-

    base required)

    22---1/8

    (562)

    19

    (483)

    23---3/4

    (603)

    20---5/8

    (600)

    Downflow Applications on Combustible Flooring with CNPV,

    CNRV, CAR, or CAP Coil Assembly or KCAKC coil box

    (KGASB subbase not required)

    22---1/2

    (572)

    19

    (483)

    23---1/2

    (597)

    20

    (508)

    HORIZONTAL INSTALLATION

    FIRE, EXPLOSION, AND CARBON MONOXIDE

    POISONING HAZARD

    Failure to follow this warning could result in personal

    injury, death, and/or property damage.

    Do not install the furnace on its back or hang furnace with

    control compartment facing downward. Safety control

    operation will be adversely affected. Never connect

    return--air ducts to the back of the furnace.

    !

    WARNING

    The furnace can be installed horizontally in an attic or crawl space

    on either the left--hand (LH) or right --hand (RH) side. The furnace

    can be hung from floor joists, rafters or trusses or installed on a

    non -- combustible platform, blocks, bricks or pad.

    Suspended Furnace

    Support

    The furnace may be supported under each end with threaded rod,

    angle iron or metal plumber’s strap as shown. (See Fig. 15 and

    16.) Secure angle iron to bottom of furnace as shown.

    Heavy--gauge sheet metal straps (plumber’ s straps) may be used

    to suspend the furnace from each bottom corner. To prevent

    screws from pulling out, use 2 #8 x 3/4--in. (19 mm) screws into

    the side and 2 #8 x 3/4--in. (19 mm) screws in the bottom of the

    furnace casing for each strap. (See Fig. 15 and 16.) If the screws

    are attached to ONLY the furnace sides and not the bottom, the

    straps must be vertical against the furnace sides and not pull away

    from the furnace sides, so that the strap attachment screws are not

    in tension (are loaded in shear) for reliable support.

    Platform Furnace

    Support

    Construct working platform at location where all required furnace

    clearances are met. (See Fig. 2 and 17.) For furnaces with 1--in.

    (25 mm) clearance requirement on side, set furnace on

    noncombustible blocks, bricks or angle iron. For crawl space

    installations, if the furnace is not suspended from the floor joists,

    the ground underneath furnace must be level and the furnace set

    on blocks or bricks.

    Roll--Out Pr

    otection

    Provide a minimum 17 --3/4 in. x 22 in. (451 mm x 559 mm)

    piece of sheet metal for flame roll --out protection in front of

    burner area for furnaces closer than 12 inches (305 mm) above

    the combustible deck or suspended furnaces closer than 12 inches

    (305 mm) to joists. The sheet metal MUST extend underneath the

    furnace casing by 1 in. (25 mm) with the door removed.

    The bottom closure panel on furnaces of widths 17--1/2 in. (445

    mm) and larger may be used for flame roll--out protection when

    bottom of furnace is used for return air connection. See Fig. 17

    for proper orientation of roll--out shield.

    Bottom Return Air

    Inlet

    These furnaces are shipped with bottom closure panel installed in

    bottom return-- air opening. Remove and discard this panel when

    bottom return air is used. To remove bottom closure panel,

    perform the following:

    1. Tilt or raise furnace and remove two screws holding

    bottom filler panel. (See Fig. 9.)

    2. Rotate bottom filler panel downward to release holding

    tabs.

    313A

  • Page 14:

    14

    3. Remove bottom closure panel.

    4. Reinstall bottom filler panel and screws. Side Return Air

    Inlet

    Side Return Air

    Inlet

    These furnaces are shipped with bottom closure panel installed in

    bottom return-- air opening. This panel MUST be in place when

    side return air inlet(s) is used without a bottom return air inlet.

    Not all horizontal furnaces are approved for side return air

    connections. (See Fig. 20).

    FILTER

    ARRANGEMENT

    CARBON MONOXIDE AND POISONING

    HAZARD

    Failure to follow this warning could result in personal

    injury, or death.

    Never operate a furnace without a filter or with filter access

    door removed.

    !

    WARNING

    There are no provisions for an internal filter rack in these

    furnaces.

    Deluxe furnaces are shipped with a factory supplied Media Filter

    Cabinet. The Media Filter Cabinet uses either the

    factory--supplied standard 3/4--in. (19 mm) filter or a 4--in. (102

    mm) wide Media Filter which can be purchased separately.

    Refer to the instructions supplied with media Cabinet for

    assembly and installation options.

    AIR

    DUCTS

    General Requir

    ements

    The duct system should be designed and sized according to

    accepted national standards such as those published by: Air

    Conditioning Contractors Association (ACCA), Sheet Metal and

    Air Conditioning Contractors National Association (SMACNA)

    or American Society of Heating, Refrigerating and Air

    Conditioning Engineers (ASHRAE) or consult The Air Systems

    Design Guidelines reference tables available from your local

    distributor. The duct system should be sized to handle the

    required system design CFM at the design external static pressure.

    The furnace airflow rates are provided in Table 5 --AIR

    DELIVERY--CFM (With Filter).

    When a furnace is installed so that the supply ducts carry air

    circulated by the furnace to areas outside the space containing the

    furnace, the return air shall also be handled by duct(s) sealed to

    the furnace casing and terminating outside the space containing

    the furnace.

    Secure ductwork with proper fasteners for type of ductwork used.

    Seal supply-- and return--duct connections to furnace with code

    approved tape or duct sealer.

    NOTE: Flexible connections should be used between ductwork

    and furnace to prevent transmission of vibration. Ductwork

    passing through unconditioned space should be insulated and

    sealed to enhance system performance. When air conditioning is

    used, a vapor barrier is recommended.

    Maintain a 1--in. (25 mm) clearance from combustible materials

    to supply air ductwork for a distance of 36 in. (914 mm)

    horizontally from the furnace. See NFPA 90B or local code for

    further requirements.

    Ductwo rk Acoustical Tr

    eatment

    NOTE: Metal duct systems that do not have a 90 degree elbow

    and 10 ft. (3 M) of main duct to the first branch take--off may

    require internal acoustical lining. As an alternative, fibrous

    ductwork may be used if constructed and installed in accordance

    with the latest edition of SMACNA construction standard on

    fibrous glass ducts. Both acoustical lining and fibrous ductwork

    shall comply with NFPA 90B as tested by UL Standard 181 for

    Class 1 Rigid air ducts.

    Supply Air

    Connections

    For a furnace not equipped with a cooling coil, the outlet duct

    shall be provided with a removable access panel. This opening

    shall be accessible when the furnace is installed and shall be of

    such a size that the heat exchanger can be viewed for possible

    openings using light assistance or a probe can be inserted for

    sampling the airstream. The cover attachment shall prevent leaks.

    Upflow and Horizontal Furnaces

    Connect supply --air duct to flanges on furnace supply--air outlet.

    Bend flange upward to 90_ with wide duct pliers. (See Fig. 14.)

    The supply --air duct must be connected to ONLY the furnace

    supply --outlet--air duct flanges or air conditioning coil casing

    (when used). DO NOT cut main furnace casing side to attach

    supply air duct, humidifier, or other accessories. All accessories

    MUST be connected to duct external to furnace main casing.

    NOTE: For horizontal applications, the top-- most flange may be

    bent past 90 degrees to allow the evaporator coil to hang on the

    flange temporarily while the remaining attachment and sealing of

    the coil are performed.

    Downflow

    Furnaces

    Connect supply-- air duct to supply--air outlet on furnace. Bend

    flange inward past 90_ with wide duct pliers. (See Fig. 14.) The

    supply --air duct must be connected to ONLY the furnace

    supplyoutlet or air conditioning coil casing (when used). When

    installed on combustible material, supply --air duct must be

    connected to ONLY the accessory subbase KGASB0201ALL or

    a factory approved air conditioning coil casing. DO NOT cut

    main furnace casing to attach supply side air duct, humidifier, or

    other accessories. All accessories MUST be connected to duct

    external to furnace casing.

    313A

  • Page 15:

    15

    UPFLOW DOWNFLOW HORIZONTAL

    YES

    NO

    NO

    YES

    YES

    YES

    NO

    120°

    MIN

    YES

    120°

    MIN

    YES

    120°

    MIN

    90°

    90°

    A02020

    Fig. 14 -- Duct Flanges

    1

    / 4 " (6mm) THREADED ROD

    4 REQ.

    SECURE ANGLE

    IRON TO BOTTOM

    OF FURNACE WITH

    3 #8 x

    3

    /4" (19mm) SCREWS

    TYPICAL FOR 2 SUPPORTS

    1” (25mm) SQUARE, 1-1/4”x1-1/4”x1/8” (32x32x3mm)

    ANGLE IRON OR UNI-STRUT MAY BE USED

    (2) HEX NUTS, (2) WASHERS & (2) LOCK WASHERS

    REQ. PER ROD

    8" (203mm)

    MIN

    FOR DOOR REMOVAL

    OUTER DOOR

    A S SEMBLY

    A05027

    Fig. 15 -- Horizontal Unit Suspension

    313A

  • Page 16:

    16

    METHOD 2

    USE (4) #8 x 3/4 (19 mm) SHEET

    METAL SCREWS FOR EACH

    STRAP. THE STRAPS

    SHOULD BE VERTICAL

    AGAINST THE FURNACE

    SIDES AND NOT PULL AWAY

    FROM THE FURNACE

    SIDES.

    METHOD 1

    FOLD ALL STRAPS UNDER

    FURNACE AND SECURE WTH

    (4) #8 x 3/4 (19 mm) SHEET METAL SCREWS

    (2 SCREWS IN SIDE AND 2 SCREWS

    IN BOTTOM).

    A03176

    Fig. 16 -- Horizontal Suspension with Straps

    30-IN . (762mm)

    MIN WORK AREA

    6 ″ M IN

    *

    TYPE-B

    VENT

    17

    3

    /

    4

    22

    SHEET

    MET AL

    SEDIMENT

    TRAP

    EQUIPMENT MANU AL

    SHUT -OFF GAS VA LV E

    LINE CONT A CT ONL Y PERMISSIBLE BETWEEN

    LINES FORMED BY INTERSECTIONS OF

    THE T OP AND TW O SIDES OF THE FURNA CE

    JA CKET AND BUILDING JOISTS ,

    STUDS , OR FRAMING.

    GAS

    ENTR Y

    17

    3

    /

    4

    (451mm)

    OVERALL

    4

    3

    /

    4

    (121mm)

    UNDER DOOR

    1 ″

    (25mm)

    UNDER FURNACE

    EXTEND OUT 12 ″

    (305mm)

    FR OM FA CE OF DOOR

    * WHEN USED W ITH

    SINGLE W ALL VEN T

    CONNECTIONS

    UNION

    (152mm)

    (451mm)

    (559mm)

    A03177

    Fig. 17 -- Typical Attic Installation

    313A

  • Page 17:

    17

    Retu rn Air

    Connections

    FIRE HAZARD

    Failure to follow this warning could cause personal injury,

    death and/or property damage.

    Never connect return--air ducts to the back of the furnace.

    Follow instructions below

    !

    WARNING

    Downflow Furnaces

    The return --air duct must be connected to return --air opening

    (bottom inlet) as shown in Fig. 19. DO NOT cut into casing sides

    (left or right). Side opening is permitted for only upflow and most

    horizontal furnaces. (See Fig. 19.) Bypass humidifier connections

    should be made at ductwork or coil casing sides exterior to

    furnace.

    Upflow and Horizontal Furnaces

    The return-- air duct must be connected to bottom, sides (left or

    right), or a combination of bottom and side(s) of main furnace

    casing as shown in Fig. 18 and 20. Bypass humidifier may be

    attached into unused return air side of the furnace casing. (See

    Fig. 18 and 20.)

    Not all horizontal furnaces are approved for side return air

    connections. (See Fig. 20.)

    GAS

    PIPING

    FIRE OR EXPLOSION HAZARD

    Failure to follow this warning could result in personal

    injury, death, and/or property damage.

    Never purge a gas line into a combustion chamber. Never

    test for gas leaks with an open flame. Use a commercially

    available soap solution made specifically for the detection

    of leaks to check all connections.

    !

    WARNING

    FIRE OR EXPLOSION HAZARD

    Failure to follow this warning could result in personal

    injury,death, and/or property damage.

    Use proper length of pipe to avoid stress on gas control

    manifold and a gas leak.

    !

    WARNING

    FURNACE OVERHEAT HAZARD

    Failure to follow this caution may result in property

    damage.

    Connect gas pipe to gas valve using a backup wrench to

    avoid damaging gas controls and burner misalignment.

    CAUTION

    !

    FIRE OR EXPLOSION HAZARD

    Failure to follow this warning could result in personal

    injury, death, and/or property damage.

    If local codes allow the use of a flexible gas appliance

    connector, always use a new listed connector. Do not use a

    connector which has previously served another gas

    appliance. Black iron pipe shall be installed at the furnace

    gas control valve and extend a minimum of 2 in.(51 mm)

    outside the furnace.

    !

    WARNING

    Gas piping must be installed in accordance with national and

    local codes. Refer to current edition of NFGC in the U.S., the

    CAN/CSA--B149.1 --05 in Canada.

    Installations must be made in accordance with all authorities

    having jurisdiction. If possible, the gas supply line should be a

    separate line running directly from meter to furnace.

    NOTE: In the state of Massachusetts:

    1. Gas supply connections MUST be performed by a

    licensed plumber or gas fitter .

    2. When flexible connectors are used, the maximum length

    shall not exceed 36 inches (915 mm).

    3. When lever handle type manual equipment shutoff valves

    are used, they shall be T--handle valves.

    4. The use of copper tubing for gas piping is NOT approved

    by the state of Massachusetts.

    Refer to Table 6 for recommended gas pipe sizing. Risers must be

    used to connect to furnace and to meter. Support all gas piping

    with appropriate straps, hangers, etc. Use a minimum of 1 hanger

    every 6 ft. (2 M). Joint compound (pipe dope) should be applied

    sparingly and only to male threads of joints. Pipe dope must be

    resistant to the action of propane gas.

    An accessible manual equipment shutof f valve MUST be

    installed external to furnace casing and within 6 ft. (2 M) of

    furnace. A 1/8--in. (3 mm) NPT plugged tapping, accessible for

    test gauge connection, MUST be installed immediately upstream

    of gas supply connection to furnace and downstream of manual

    equipment shutoff valve.

    NOTE: The furnace gas control valve inlet pressure tap

    connection is suitable to use as test gauge connection providing

    test pressure DOES NOT exceed maximum 0.5 psig (14--in. wc)

    stated on gas control valve. (See Fig. 52.)

    Some installations require gas entry on right side of furnace (as

    viewed in upflow.) (See Fig. 21.)

    Install a sediment trap in riser leading to furnace as shown in Fig

    22. Connect a capped nipple into lower end of tee. Capped nipple

    should extend below level of furnace gas controls. Place a ground

    joint union between furnace gas control valve and exterior

    manual equipment gas shutoff valve. A 1/8-- in. (3 mm) NPT

    plugged tapping, accessible for test gauge connection, MUST be

    installed immediately upstream of gas supply connection to

    furnace and downstream of manual equipment shutoff valve.

    313A

  • Page 18:

    18

    Table 5 – Air Delivery -- CFM (With Filter)*

    UNIT SIZE

    RETURN---AIR

    SUPPLY

    SPEED

    EXTERNAL STATIC PRESSURE (In. wc)

    0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

    045---08/

    024045

    Bottom or

    Side(s)

    5 1185 1145 1115 1075 1035 980 905 820 720 580

    4 920 880 835 800 755 720 680 645 605 540

    3 735 685 625 585 530 490 435 395 345 295

    2 820 765 725 670 630 580 545 490 455 405

    1 650 595 535 490 430 390 330 280 235 --- ---

    070---16 /

    048070

    Bottom or

    Side(s)

    5 1625 1585 1535 1495 1460 1415 1365 1295 1220 1125

    4 1405 1360 1320 1280 1240 1195 1155 1115 1070 1030

    3 1240 1200 1155 1110 1065 1020 975 935 895 850

    2 1190 1140 1095 1050 1000 955 915 870 830 790

    1 1035 985 930 885 835 785 745 695 650 600

    090---16 /

    048090

    Bottom or

    Side(s)

    5 1845 1800 1755 1710 1665 1595 1500 1400 1275 1105

    4 1590 1545 1500 1455 1410 1365 1315 1270 1180 1000

    3 1365 1320 1270 1215 1170 1125 1070 1025 955 900

    2 1225 1160 1110 1060 1010 950 895 830 770 710

    1 1100 1030 960 875 805 730 645 570 505 425

    110---20 /

    060110

    Bottom or

    Side(s)

    5 2255 2205 2150 2100 2040 1985 1920 1835 1735 1615

    4 1600 1525 1465 1400 1335 1275 1210 1150 1080 1015

    3 1945 1890 1830 1770 1715 1655 1600 1545 1480 1430

    2 1420 1340 1280 1200 1140 1065 1005 925 865 790

    1 1280 1205 1140 1055 990 910 840 760 695 630

    135---20 /

    060135

    Bottom or

    Side(s)

    5 2295 2240 2185 2125 2070 2005 1925 1805 1670 1545

    4 1725 1660 1605 1545 1460 1395 1340 1285 1230 1170

    3 1910 1865 1800 1745 1685 1610 1545 1485 1435 1380

    2 1630 1575 1510 1435 1365 1300 1245 1185 1130 1065

    1 1430 1355 1285 1200 1125 1075 1015 945 855 800

    *A filter is required for each return ---air inlet. Airflow performance included 3/4 ---in. (19 mm) washable filter media such as contained in factory --- a u t h o r i z e d

    accessory filter rack. To determine airflow performance with out this filter, assu me an additional 0.1 in. wc available external static pressu re.

    --- --- Indicates unstable operating conditions.

    Table 6 – Maximum Capacity of Pipe*

    NOMINAL IRON

    PIPE

    INTERNAL

    DIAMETER

    LENGTH OF PIPE --- FT. (M)

    SIZE IN. (mm) In. (mm) 10 20 30 40 50

    1/2 ( 13) 0.622 (16) 175 (53) 120 (37) 97 (30) 82 (25) 73 (22)

    3/4 ( 19) 0.824 (21) 360 (110) 250 (76) 200 (61) 170 (52) 151 (46)

    1 (25) 1.049 (27) 680 (207) 465 (142) 375 (114) 320 (98) 285 ( 87)

    1---1/4 (32) 1.380 (35) 1400 (427) 950 ( 290) 770 ( 235) 660 (201) 580 (177)

    1---1/2 (38) 1.610 (41) 2100 (640) 1460 (445) 1180 (360) 990 ( 301) 900 (274)

    * C u bic ft. of natural gas per h r for gas pressures of 0.5 psig (14---in. wc) or l ess and a pressure drop of 0.5---in wc (based on a 0.60 specific gravity

    gas). Ref: Chapter 6 ANSI Z223---2006/NFPA 54 ---2006.

    Piping should be pressure and leak tested in accordance with

    NFGC in the United States or CAN/CSA-- B149.1 --05 in Canada,

    local, and national plumbing and gas codes before the furnace has

    been connected. After all connections have been made, purge

    lines and check for leakage at furnace prior to operating furnace.

    If pressure exceeds 0.5 psig (14--in. wc), gas supply pipe must be

    disconnected from furnace and capped before and during supply

    pipe pressure test. If test pressure is equal to or less than 0.5 psig

    (14-- in. wc), turn off electric shutoff switch located on furnace gas

    control valve and accessible manual equipment shutof f valve

    before and during supply pipe pressure test. After all connections

    have been made, purge lines and check for leakage at furnace

    prior to operating furnace.

    The gas supply pressure shall be within the maximum and

    minimum inlet supply pressures marked on the rating plate with

    the furnace burners ON and OFF.

    313A

  • Page 19:

    19

    A02075

    Fig. 18 -- Upflow Return Air Configurations and Restrictions

    A02163

    Fig. 19 -- Downflow Return Air Configurations and Restrictions

    313A

  • Page 20:

    20

    A02162

    Fig. 20 -- Horizontal Return Air Configurations and Restrictions

    2” (51mm)

    Street Elbow

    A08551

    Fig. 21 -- Burner and Manifold

    313A

  • Page 21:

    21

    Table 7 – Electrical Data

    FURNACE

    MODEL

    V O LT S ---

    H E R T Z ---

    PHASE

    OPERATING

    VOLTAGE*

    (VOLTS)

    MAX UNIT

    (AMPS)

    UNIT

    AMPACITY#

    (AMPS)

    MAX WIRE

    LENGTH

    }

    FT. (M)

    MAX FUSE/

    CKT BKR

    {

    (AMPS)

    MIN WIRE

    GAGE

    MAX MIN

    045---08 / 024045 1 1 5 --- 6 0 --- 1 127 104 8.1 10.9 34 (10) 15 14

    070---16 / 048070 1 1 5 --- 6 0 --- 1 127 104 9.5 12.6 29 (9) 15 14

    090---16 / 048090 1 1 5 --- 6 0 --- 1 127 104 10.3 13.4 27 (8) 15 14

    110---20 / 060110 1 1 5 --- 6 0 --- 1 127 104 13.1 16.9 34 (10) 20 12

    135---20 / 060135 1 1 5 --- 6 0 --- 1 127 104 13.1 16.9 34 (10) 20 12

    * Permissible limits of the voltage range at which the unit operates satisfactorily .

    # Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of all other potential operating components’ (EAC, humidifier,

    etc.) full load a mps.

    { Time---delay type is r ecommended.

    } Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.

    UNION

    SEDIMENT

    TRAP

    MANUAL

    SHUTOFF

    VALVE

    (REQUIRED)

    GAS

    SUPPLY

    A02035

    Fig. 22 -- Typical Gas Pipe Arrangement

    ELECTRICAL

    CONNECTIONS

    ELECTRICAL SHOCK HAZARD

    Failure to follow this warning could result in personal

    injury or death.

    Blower access panel door switch opens 115--v power to

    control. No component operation can occur. Do not bypass

    or close switch with panel removed.

    !

    WARNING

    See Fig. 25 for field wiring diagram showing typical field 115--v

    wiring. Check all factory and field electrical connections for

    tightness.

    Field--supplied wiring shall conform with the limitations of 63_F

    (35_C) rise.

    ELECTRICAL SHOCK AND FIRE HAZARD

    Failure to follow this warning could result in personal

    injury, death, or property damage.

    The cabinet MUST have an uninterrupted or unbroken

    ground according to NEC ANSI/NFPA 70--2008 and

    Canadian Electrical Code CSA C22.1 or local codes to

    minimize personal injury if an electrical fault should occur.

    This may consist of electrical wire, conduit approved for

    electrical ground or a listed, grounded power cord (where

    permitted by local code) when installed in accordance with

    existing electrical codes. Refer to the power cord

    manufacturer’s ratings for proper wire gauge. Do not use

    gas piping as an electrical ground.

    !

    WARNING

    313A

  • Page 22:

    22

    FURNACE MAY NOT OPERATE

    Failure to follow this caution may result in intermittent

    furnace operation.

    Furnace control must be grounded for proper operation or

    else control will lock out. Control must remain grounded

    through green/yellow wire routed to gas valve and manifold

    bracket screw.

    CAUTION

    !

    115--V WIRING

    Verify that the voltage, frequency, and phase correspond to that

    specified on unit rating plate. Also, check to be sure that service

    provided by utility is sufficient to handle load imposed by this

    equipment. Refer to rating plate or Table 7 for equipment

    electrical specifications.

    U.S. Installations: Make all electrical connections in accordance

    with National Electrical Code (NEC) ANSI/NFPA 70 --2008 and

    any local codes or ordinances that might apply .

    Canadian Installations: Make all electrical connections in

    accordance with Canadian Electrical Code CSA C22.1 or

    authorities having jurisdiction.

    FIRE HAZARD

    Failure to follow this warning could result in personal

    injury, death, or property damage.

    Do not connect aluminum wire between disconnect switch

    and furnace. Use only copper wire.

    !

    WARNING

    Use a separate, fused branch electrical circuit with a properly

    sized fuse or circuit breaker for this furnace. See T able 7 for wire

    size and fuse specifications. A readily accessible means of

    electrical disconnect must be located within sight of the furnace.

    NOTE: Proper polarity must be maintained for 115--v wiring. If

    polarity is incorrect, control LED status indicator light will flash

    rapidly and furnace will NOT operate.

    J --BOX RELOCA

    TION

    NOTE: If factory location of J--Box is acceptable, go to next

    sectio n (ELECTRICAL CONNECTION TO J--BOX).

    NOTE: On 14-- in. (356 mm) wide casing models, the J-- Box

    shall not be relocated to other side of furnace casing when the

    vent pipe is routed within the casing.

    1. Remove and save two screws holding J--Box.

    NOTE: The J--Box cover need not be removed from the J--Box

    in order to move the J-- Box. Do NOT remove green ground

    screw inside J --Box. The ground screw is not threaded into the

    casing flange and can be lifted out of the clearance hole in casing

    while swinging the front edge of the J--Box outboard of the

    casing.

    2. Cut wire tie on loop in furnace wires attached to J-- box.

    3. Move J-- Box to desired location.

    4. Fasten J--Box to casing with two screws removed in Step

    1.

    5. Route J--Box wires within furnace away from sharp edges,

    rotating parts and hot surfaces.

    ELECTRICAL CONNECTION TO

    J--BOX

    Field--Supplied Electrical Box on Furnace J--Box Bracket

    See Fig. 23.

    1. Remove cover from furnace J--Box.

    2. Attach electrical box to furnace J--Box bracket with at least

    two field-- supplied screws through holes in electrical box

    into holes in bracket. Use blunt-- nose screws that will not

    pierce wire insulation.

    3. Route furnace power wires through holes in electrical box

    and J--Box bracket, and make field--wire connections in

    electrical box. Use best practices (NEC in U.S. and CSA

    C22.1 in Canada) for wire bushings, strain relief, etc.

    4. Route and secure field ground wire to green ground screw

    on J-- Box bracket.

    5. Connect line voltage leads as shown in Fig. 25.

    6. Reinstall cover to J--Box. Do not pinch wires between

    cover and bracket.

    Electrical Box on Furnace Casing Side

    See Fig. 23.

    FIRE OR ELECTRICAL SHOCK HAZARD

    Failure to follow this warning could result in personal

    injury, death, or property damage.

    If field --supplied manual disconnect switch is to be mounted

    on furnace casing side, select a location where a drill or

    fastener cannot damage electrical or gas components.

    !

    WARNING

    1. Select and remove a hole knockout in the casing where the

    electrical box is to be installed.

    NOTE: Check that duct on side of furnace will not interfere with

    installed electrical box.

    2. Remove the desired electrical box hole knockout and

    positionthe hole in the electrical box over the hole in the

    furnace casing.

    3. Fasten the electrical box to casing by driving two

    fieldsupplied screws from inside electrical box into casing

    steel.

    4. Remove and save two screws holding J-- Box. (See Fig.

    22.)

    5. Pull furnace power wires out of 1/2--in. (12 mm) diameter

    hole in J-- Box. Do not loosen wires from strain --relief

    wire--tie on outside of J-- Box.

    6. Route furnace power wires through holes in casing and

    electrical box and into electrical box.

    7. Pull field power wires into electrical box.

    8. Remove cover from furnace J--Box.

    9. Route field ground wire through holes in electrical box

    and casing, and into furnace J-- Box.

    10. Reattach furnace J--Box to furnace casing with screws

    removedinStep4.

    11. Secure field ground wire to J-- Box green ground screw.

    12. Complete electrical box wiring and installation. Connect

    line voltage leads as shown in Fig. 25. Use best practices

    (NEC in U.S. and CSA C22.1 in Canada) for wire

    bushings, strain relief, etc.

    13. Reinstall cover to J--Box. Do not pinch wires between

    cover and bracket.

    313A

  • Page 23:

    23

    A03221

    Fig. 23 -- Field --Supplied Electrical Box on Furnace Casing

    POWER CORD INSTALLATION IN FURNACE

    J--BOX

    NOTE: Power cords must be able to handle the electrical

    requirements listed in Table 7. Refer to power cord

    manufacturer’s listings.

    1. Remove cover from J--Box.

    2. Route listed power cord through 7/8--in. (22 mm) diameter

    hole in J-- Box.

    3. Secure power cord to J--Box bracket with a strain relief

    bushing or a connector approved for the type of cord used.

    4. Secure field ground wire to green ground screw on J--Box

    bracket.

    5. Connect line voltage leads as shown in Fig. 25.

    6. Reinstall cover to J--Box. Do not pinch wires between

    cover and bracket.

    BX CABLE INSTALLATION IN FURNACE

    J--BOX

    1. Remove cover from J--Box.

    2. Route BX cable into 7/8--inch diameter hole in J-- Box.

    3. Secure BX cable to J--Box bracket with connectors

    approved for the type of cable used.

    4. Secure field ground wire to green ground screw on J--Box

    bracket.

    5. Connect line voltage leads as shown in Fig. 25.

    6. Reinstall cover to J--Box. Do not pinch wires between

    cover and bracket.

    24 -- V

    WIRING

    Make field 24 --v connections at the 24--v terminal strip. (See Fig.

    23.) Connect terminal Y/Y2 as shown in Fig. 24 for proper

    cooling operation. Use only AWG No. 18, color--coded, copper

    thermostat wire.

    The 24--v circuit contains an automotive--type, 3 --amp.. fuse

    located on the control. Any direct shorts during installation,

    service, or maintenance could cause this fuse to blow. If fuse

    replacement is required, use ONLY a 3--amp.. fuse of identical

    size.

    ACCESSORIES

    1. Electronic Air Cleaner (EAC)

    Connect an accessory Electronic Air Cleaner (if used)

    using 1/4--in female quick connect terminals to the two

    male 1/4--in quick -- connect terminals on the control board

    marked EAC--1 and EAC--2. The terminals are rated for

    115 VAC, 1.0 amps maximum and are energized during

    blower motor operation. (See Fig. 24.)

    2. Humidifier (HUM)

    Connect an accessory 24 VAC, 0.5 amp. maximum

    humidifier (if used) to the 1/4 -- in male quick-- connect

    HUM terminal and COM--24V screw terminal on the

    control board thermostat strip. The HUM terminal is

    energized when gas valve relay (GVR) is energized. (See

    Fig. 24.)

    NOTE: A field--supplied, 115--v controlled relay connected to

    EAC terminals may be added if humidifier operation is desired

    during blower operation.

    NOTE: DO NOT connect furnace control HUM terminal to

    HUM (humidifier) terminal on Thermidistatt, Zone Controller

    or similar device. See Thermidistat, Zone Controller, thermostat,

    or controller manufacturer’s instructions for proper connection.

    VENTING

    The furnace shall be connected to a listed factory built chimney

    or vent, or a clay--tile lined masonry or concrete chimney. Venting

    into an unlined masonry chimney or concrete chimney is

    prohibited.

    When an existing Category I furnace is removed or replaced, the

    original venting system may no longer be sized to properly vent

    the attached appliances. An improperly sized Category I venting

    system could cause the formation of condensate in the furnace

    and vent, leakage of condensate and combustion products, and

    spillage of combustion products into the living space.

    313A

  • Page 24:

    24

    BLOWER OFF-DELAY

    24-V THERMOSTAT

    TERMINALS

    3-AMP FUSE

    LED OPERATION

    & DIAGNOSTIC

    LIGHT

    BLOWER SPEED

    SELECTION

    TERMINALS

    HEAT

    FAN

    COOL

    SPARE 2

    SPARE 1

    115-VAC (L2)

    NEUTRAL

    CONNECTIONS

    115-VAC (L1)

    NEUTRAL

    CONNECTIONS

    EAC-1 TERMINAL

    (115-VAC 1.0 AMP. MAX.)

    PL2-HOT SURFACE

    IGNITER & INDUCER

    MOTOR CONNECTOR

    PL1-LOW VOLTAGE

    DRAIN HARNESS

    CONNECTOR

    TRANSFORMER

    24-VAC CONNECTIONS

    HUMIDIFIER TERMINAL

    (24-VAC 0.5 AMP. MAX)

    TWINNING AND/OR

    COMPONENT TEST

    TERMINAL

    A08063

    Fig. 24 -- Furnace Control

    115-V FIELD-

    SUPPLIED

    DISCONNECT

    AUXILIARY

    J-BOX

    24-V

    TERMINAL

    BLOCK

    THREE-WIRE

    HEATING-ONLY

    FIVE WIRE

    NOTE 1

    NOTE 2

    FIELD-SUPPLIED

    DISCONNECT

    CONDENSING

    UNIT

    TWO

    WIRE

    FURNACE

    C

    O

    N

    T

    R

    O

    L

    R

    G

    COM

    WCR GY

    GND

    GND

    FIELD 24-V WIRING

    FIELD 115-, 208/230-, 460-V WIRING

    FACTORY 24-V WIRING

    FACTORY 115-V WIRING

    208/230- OR

    460-V

    THREE

    PHASE

    208/230-V

    SINGLE

    PHASE

    BLOWER DOOR SWITCH

    WHT

    BLK

    WHT

    BLK

    NOTES: Connect Y-terminal in furnace as shown for proper blower operation.

    Some thermostats require a "C" terminal connection as shown.

    If any of the original wire, as supplied, must be replaced, use

    same type or equivalent wire.

    W

    Y/Y2

    GND

    THERMOSTAT

    TERMINALS

    1.

    2.

    3.

    A99440

    Fig. 25 -- Heating and Cooling Application Wiring Diagram with 1 --Stage Thermostat

    313A

  • Page 25:

    25

    CARBON MONOXIDE POISONING HAZARD

    Failure to follow the steps outlined below for each

    appliance connected to the venting system being placed into

    operation could result in carbon monoxide poisoning or

    death. The following steps shall be followed for each

    appliance connected to the venting system being placed into

    operation, while all other appliances connected to the

    venting system are not in operation:

    1. Seal any unused openings in venting system.

    2. Inspect the venting system for proper size and

    horizontal pitch, as required in the National Fuel Gas

    Code, ANSI Z223.1/NFPA 54 or CSA B149.1,

    Natural Gas and Propane Installation Code and these

    instructions. Determine that there is no blockage or

    restriction, leakage, corrosion and other deficiencies,

    which could cause an unsafe condition.

    3. As far as practical, close all building doors and

    windows and all doors between the space in which

    the appliance(s) connected to the venting system are

    located and other spaces of the building.

    4. Close fireplace dampers.

    5. Turn on clothes dryers and any appliance not

    connected to the venting system. Turn on any

    exhaust fans, such as range hoods and bathroom

    exhausts, so they are operating at maximum speed.

    Do not operate a summer exhaust fan.

    6. Follow the lighting instructions. Place the appliance

    being inspected into operation. Adjust the thermostat

    so appliance is operating continuously.

    7. Test for spillage from draft hood equipped

    appliances at the draft hood relief opening after 5

    minutes of main burner operation. Use the flame of a

    match or candle.

    8. If improper venting is observed during any of the

    above tests, the venting system must be corrected in

    accordance with the National Fuel Gas Code, ANSI

    Z223.1/NFPA 54 and/or CSA B149.1, Natural Gas

    and Propane Installation Code.

    9. After it has been determined that each appliance

    connected to the venting system properly vents when

    tested as outlined above, return doors, windows,

    exhaust fans, fireplace dampers and any other

    gas-- fired burning appliance to their previous

    conditions of use.

    !

    WARNING

    Vent system or vent connectors may need to be resized. Vent

    systems or vent connectors, must be sized to approach minimum

    size as determined using appropriate table found in the NFGC or

    CAN/CSA--B149.1--05.

    GENERAL VENTING

    REQUIREMENTS

    Follow all safety codes for proper vent sizing and installation

    requirements, including local building codes, the National Fuel

    Gas Code ANSI Z223.1--2006/NFPA 54--2006 (NFGC), Parts 12

    and 13 in the United States or the National Standard of Canada,

    Natural Gas and Propane Installation Code CSA --B149.1--05

    (CAN/CSA--B149.1 --05), Section 8 and Appendix C in Canada,

    the local building codes, and furnace and vent manufacturers’

    instructions.

    These furnaces are design--certified as Category I furnaces in

    accordance with ANSI Z21.47--2006/CSA 2.3--2006 and operate

    with a non--positive vent static pressure to minimize the potential

    for vent gas leakage. Category I furnaces operate with a flue loss

    not less than 17 percent to minimize the potential for

    condensation in the venting system. These furnaces are approved

    for common venting and multistory venting with other fan

    assisted or draft hood equipped appliances in accordance with the

    NFGC or the CAN/CSA--B149.1 -- 05, the local building codes,

    and furnace and vent manufacturers’ instructions. The following

    information and warning must be considered in addition to the

    requirements defined in the NFGC and the

    CAN/CSA--B149.1--05.

    1. If a vent (common or dedicated) becomes blocked, the

    furnace will be shut off by the draft safeguard switch

    located on the vent elbow.

    2. Do not vent this Category I furnace into a single-- wall

    dedicated or common vent. The dedicated or common

    vent is considered to be the vertical portion of the vent

    system that terminates outdoors.

    3. Vent connectors serving Category I furnaces shall not be

    connected into any portion of a mechanical draft system

    operating under positive pressure.

    4. In the U.S.: Do not vent this appliance with any solid fuel

    burning appliance. In Canada: Check with the authority

    having jurisdiction for approval on use with solid fuel

    burning appliance.

    5. Category I furnaces must be vented vertically or nearly

    vertically unless equipped with a listed power ventor.

    6. Do not vent this appliance into an unlined masonry

    chimney. Refer to Chimney Inspection Chart, Fig. 33.

    MASONRY CHIMNEY

    REQUIREMENTS

    NOTE: These furnaces are CSA design--certified for use in

    exterior tile--lined masonry chimneys with a factory accessory

    Chimney Adapter Kit. Refer to the furnace rating plate for correct

    kit usage. The Chimney Adapter Kits are for use with ONLY

    furnaces having a Chimney Adapter Kit numbers marked on the

    furnace rating plate.

    If a clay tile--lined masonry chimney is being used and it is

    exposed to the outdoors below the roof line, relining might be

    required. Chimneys shall conform to the Standard for Chimneys,

    Fireplaces, Vents, and Solid Fuel Burning Appliances

    ANSI/NFPA 211-- 2006 in the United States and to a Provincial or

    Territorial Building Code in Canada (in its absence, the National

    Building Code of Canada) and must be in good condition.

    U.S.A.--Refer to Sections 13.1.8 and 13.2.20 of the NFGC

    NFPA54/ANSI Z223.1-- 2006 or the authority having jurisdiction

    to determine whether relining is required. If relining is required,

    use a properly sized listed metal liner, Type--B vent, or a listed

    alternative venting design.

    NOTE: See the NFPA54/ANSI Z223.1-- 2006, 13.1.8 and

    13.2.20 regarding alternative venting design and the Exception,

    which cover installations such as the Chimney Adapter Kits

    KGACA02014FC and KGACA02015FC, which are listed for

    use with these furnaces.

    The Chimney Adapter Kit is listed alternative venting system for

    these furnaces. See the kit instructions for complete details.

    313A

  • Page 26:

    26

    See notes 2,5,7, and 10 on the page following these figures.

    A04215

    Fig. 26 -- Single--Stage Furnace with Single--Speed Air Con-

    ditioner

    See notes 2,5,8, and 10 on the page following these figures.

    A04216

    Fig. 27 -- Single Stage Furnace with Two--Speed Air Condi-

    tioner

    See notes 1, 2, 4, 6, 7, 9, 10 and 12 on the

    page following these figures.

    A04217

    Fig. 28 -- Single--Stage Furnace with Single--Speed Heat

    Pump (Dual Fuel)

    See notes 1, 2, 3, 4, 6, 8, 9, 10 and 12 on the

    page following these figures.

    A04218

    Fig. 29 -- Single-- Stage Furnace with Two--Speed heat Pump

    (Dual Fuel)

    313A

  • Page 27:

    27

    HUMIDFIER

    (24VAC)

    See notes 1, 2, 4, 11, 12, and 13 on the page following these figures.

    A04219

    Fig. 30 -- Dual Fuel Thermostat with Single--Stage Furnace

    and Single--Speed Heat Pump

    HUMIDFIER

    (24VAC)

    See notes 1, 2, 3, 4, 11, 12, and 14 on the page following these figures.

    A04220

    Fig. 31 -- Dual Fuel Thermostat with Single--Stage Furnace

    and Two-- Speed Heat Pump

    HUMIDFIER

    (24VAC)

    See note 2 on the page following these figures.

    A04221

    Fig. 32 -- Two Stage Thermostat with Single--Stage Furnace and Two--Speed Air Conditioner

    NOTES FOR FIGURES 26--32

    1. Heat pump MUST have a high pressure switch for dual fuel applications.

    2. Refer to outdoor equipment Installation Instructions for additional information and setup procedure.

    3. Outdoor Air Temperature Sensor must be attached in all dual fuel applications.

    4. Dip switch No. 1 on Thermidistat should be set in OFF position for air conditioner installations. This is factory default.

    5. Dip switch No. 1 on Thermidistat should be set in ON position for heat pump installations.

    6. Dip switch No. 2 on Thermidistat should be set in OFF position for single--speed compressor operation. This is factory default.

    7. Dip switch No. 2 on Thermidistat should be set in ON position for two--speed compressor operation.

    8. Configuration Option No. 10 “Dual Fuel Selection” must be turned ON in all dual fuel applications.

    9. NO connection should be made to the furnace HUM terminal when using a Thermidistat.

    10. The RVS Sensing terminal “L” should not be connected. This is internally used to sense defrost operation.

    11. DO NOT SELECT the “FURNACE INTERFACE” o r “BALANCE POINT” option on the two--speed heat pump control board. This

    is controlled internally by the Thermidistat/Dual Fuel Thermostat.

    12. Dip switch D on Dual Fuel Thermostat should be set in OFF position for single--speed compressor operation. This is factory default.

    13. Dip switch D on Dual Fuel Thermostat should be set in ON position for two--speed compressor operation.

    313A

  • Page 28:

    28

    Canada (and U.S.A.)--This furnace is permitted to be vented into

    a clay tile--lined masonry chimney that is exposed to the outdoors

    below the roof line, provided:

    1. Vent connector is Type--B double-- wall, and

    2. This furnace is common vented with at least 1 draft

    hoodequipped appliance, and

    3. The combined appliance input rating is less than the

    maximum capacity given in Table A, and

    4. The input rating of each space heating appliance is greater

    than the minimum input rating given in Table B for the

    local 99% Winter Design Temperature. Chimneys having

    internal areas greater than 38 square inches require furnace

    input ratings greater than the input ratings of these

    furnaces. See footnote at bottom of Table B, and

    5. The authority having jurisdiction approves.

    If all of these conditions cannot be met, an alternative venting

    design shall be used, such as the listed chimney adapter kit with

    these furnaces, which are listed for use with the kit, a listed

    chimney--lining system, or a Type--B common vent.

    Inspections before the sale and at the time of installation will

    determine the acceptability of the chimney or the need for repair

    and/or (re)lining. Refer to the Fig. 33 to perform a chimney

    inspection. If the inspection of a previously used tile--lined

    chimney:

    a. Shows signs of vent gas condensation, the chimney

    should be relined in accordance with local codes and the

    authority having jurisdiction. The chimney should be

    relined with a listed metal liner, Type--B vent, or a listed

    chimney adapter kit shall be used to reducecondensation.

    If a condensate drain is required by local code, refer to

    the NFGC NFPA54/ANSI Z223.1--2006, Section 12.10

    for additional information on condensate drains.

    b. Indicates the chimney exceeds the maximum permissible

    size in the tables, the chimney should be rebuilt or relined

    to conform to the requirements of the equipment being

    installed and the authority having jurisdiction.

    A chimney without a clay tile liner, which is otherwise in good

    condition, shall be rebuilt to conform to ANSI/NFPA 211 or be

    lined with a UL listed (ULC listed in Canada) metal liner or UL

    listed Type--B vent. Relining with a listed metal liner or Type--B

    vent is considered to be a vent--in--a--chase.

    If a metal liner or Type--B vent is used to line a chimney, no other

    appliance shall be vented into the annular space between the

    chimney and the metal liner.

    Exterior Masonry Chimney FAN + NAT

    Installations with Type--B Double Wall Vent

    Connectors ©NFPA & AGA

    Table 8 – Combined Appliance Maximum Input Rating in

    Thousands of BTUH per Hour

    VENT HEIGHT

    FT. (M)

    INTERNAL AREA OF CHIMNEY

    IN

    2

    (MM

    2

    )

    12

    (7741)

    19

    (12258)

    28

    (18064)

    38

    (24516)

    6 (1.8) 74 119 178 257

    8 (2.4) 80 130 193 279

    10 (3.0) 84 138 207 299

    15 (4.5) NR 152 233 334

    20 (6.0) NR NR 250 368

    30 (9.1) NR NR NR 404

    Table 9 – Minimum Allowable Input Rating of Space --Heat-

    ing Appliance in Thousands of BTUH per Hour

    VENT HEIGHT

    FT (M)

    INTERNAL AREA OF CHIMNEY

    IN

    2

    .(MM

    2

    )

    12

    (7741)

    19

    (12258)

    28

    (18064)

    38

    (24516)

    Local 99% Winter Design

    Temperature: 17 to 26_F ( --- 8 t o --- 3 _C)

    6 (1.8) 0 55 99 141

    8 (2.4) 52 74 111 154

    10 (3.0) NR 90 125 169

    15 (4.6) NR NR 167 212

    20 (6.1) NR NR 212 258

    30 (9.1) NR NR NR 362

    Local 99% Winter Design

    Temperature: 5 to 16_F * ( --- 1 5 t o --- 9 _C)

    6 (1.8) NR 78 121 166

    8 (2.4) NR 94 135 182

    10 (3.0) NR 111 149 198

    15 (4.6) NR NR 193 247

    20 (6.1) NR NR NR 293

    30 (9.1) NR NR NR 377

    Local 99% Winter Design

    Temperature: ---10 to 4_F * ( --- 2 3 t o --- 1 6 _C)

    6 (1.8) NR NR 145 196

    8 (2.4) NR NR 159 213

    10 (3.0) NR NR 175 231

    15 (4.6) NR NR NR 283

    20 (6.1) NR NR NR 333

    30 (9.1) NR NR NR NR

    Local 99% Winter Design

    Temperature: ---11_F ( --- 2 4 _C) or lower

    Not recommended for any vent configuration.

    *The 99.6% heating db temperatures found in the 1997 or 2001 ASHRAE

    Fundamentals Handbook, Climatic Design Information chapter, Table 1A

    (United States) and 2A (Canada) or the 2005 ASHRAE Fundamentals

    handbook, Climatic Design Information chapter, and the CD---ROM in-

    cluded with the 2005 ASHRAE Fundamental s Handbook.

    APPLIANCE APPLICATION REQUIREMENTS

    Appliance operation has a significant impact on the performance

    of the venting system. If the appliances are sized, installed,

    adjusted, and operated properly, the venting system and/or the

    appliances should not suffer from condensation and corrosion.

    The venting system and all appliances shall be installed in

    accordance with applicable listings, standards, and codes.

    The furnace should be sized to provide 100 percent of the design

    heating load requirement plus any margin that occurs because of

    furnace model size capacity increments. Heating load estimates

    can be made using approved methods available from Air

    Conditioning Contractors of America (Manual J); American

    Society of Heating, Refrigerating, and Air--Conditioning

    Engineers; or other approved engineering methods. Excessive

    oversizing of the furnace could cause the furnace and/or vent to

    fail prematurely . When a metal vent or metal liner is used, the

    vent must be in good condition and be installed in accordance

    with the vent manufacturer’ s instructions.

    313A

  • Page 29:

    29

    CHIMNEY INSPECTION CHART

    For additional requirements refer to the National Fuel Gas Code NFPA 54/ANSI Z223.1 and ANSI/NFPA 211

    Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances in the U.S.A. or to the Canadian

    installation Code CSA-B149.1 in Canada.

    Consult

    Part C of

    chimney adapter venting

    instructions for

    application

    suitability

    Is chimney

    lined with properly

    sized, listed liner or

    Type-B vent?

    Is chimney

    to be dedicated to

    a single

    furnace?

    Chimney

    exposed to

    outdoors below

    roof line?

    Repair

    liner or top seal

    or reline chimney as

    necessary.

    Mortar

    or tile

    debris?

    Clay

    tile misalignment,

    missing sections,

    gaps?

    Debris

    in cleanout?

    Mortar, tile, metal vent,

    fuel oil residue?

    Is

    liner and top

    seal in good

    condition?

    Is chimney

    property lined with

    clay tile liner?

    Crown

    condition:

    Missing mortar

    or brick?

    Rebuild

    crown.

    Ye s

    Ye s

    No

    No

    No

    Reline

    Ye s

    Repair

    Ye s

    Ye s

    Ye s

    No

    No

    Remove mortar

    and tile debris

    Remove metal vent

    or liner.

    No

    No

    No

    No

    Ye s

    Ye s

    Suitable

    Suitable

    Not Suitable

    Line chimney with property

    sized, listed flexible metal

    liner or Type-B vent per

    NFGC or NSCNGPIC Vent

    Sizing Tables and liner or

    vent manufacturer’s

    Installation instructions.

    Install chimney

    adapter per

    instructions.

    Chimney is

    acceptable for use.

    Install chimney

    adapter per

    instructions.

    Consult

    Part B of

    chimney adapter venting

    instructions for

    application

    suitability.

    Ye s

    Not Suitable

    Condensate

    drainage at bottom

    of chimney?

    Ye s

    No

    A03206

    Fig. 33 -- Chimney Inspection Chart

    313A

  • Page 30:

    30

    To prevent condensation in the furnace and vent system, the

    following precautions must be observed:

    1. The return--air temperature must be at least 60_F

    (16_C)db except for brief periods of time during warm--up

    from setback at no lower than 55_F(13_C) db or during

    initial start--up from a standby condition.

    2. Adjust the gas input rate per the installation instructions.

    Low gas input rate causes low vent gas temperatures,

    causing condensation and corrosion in the furnace and/or

    venting system. Derating is permitted only for altitudes

    above 2000 ft. (610 M).

    3. Adjust the air temperature rise to the midpoint of the rise

    range or slightly above. Low air temperature rise can cause

    low vent gas temperature and potential for condensation

    problems.

    4. Set the thermostat heat anticipator or cycle rate to reduce

    short cycling.

    Air for combustion must not be contaminated by halogen

    compounds which include chlorides, fluorides, bromides, and

    iodides. These compounds are found in many common home

    products such as detergent, paint, glue, aerosol spray, bleach,

    cleaning solvent, salt, and air freshener, and can cause corrosion

    of furnaces and vents. Avoid using such products in the

    combustion--air supply. Furnace use during construction of the

    building could cause the furnace to be exposed to halogen

    compounds, causing premature failure of the furnace or venting

    system due to corrosion.

    Vent dampers on any appliance connected to the common vent

    can cause condensation and corrosion in the venting system. Do

    not use vent dampers on appliances common vented with this

    furnace.

    ADDITIONAL VENTING

    REQUIREMENTS

    A 4” (101 mm) round vent elbow is supplied with the furnace. A

    5 -- inch (127 mm) or 6-- inch (152 mm) vent connector may be

    required for some model furnaces. A field--supplied

    4 -- inch-- to--5-- inch (101 -- 127 mm) or 4-- inch --to--6 --inch (101 --

    152 mm) sheet metal increaser fitting is required when 5--inch

    (127 mm) or 6--inch (152 mm) vent connector is used. See Fig.

    34 -- 46 Venting Orientation for approved vent configurations.

    NOTE: Vent connector length for connector sizing starts at

    furnace vent elbow. The 4 --inch vent elbow is shipped for upflow

    configuration and may be rotated for other positions. Remove the

    3 screws that secure vent elbow to furnace, rotate furnace vent

    elbow to position desired, reinstall screws. The factory--supplied

    vent elbow does NOT count as part of the number of vent

    connector elbows.

    The vent connector can exit the door through one of 5 locations

    on the door.

    1. Attach the single wall vent connector to the furnace vent

    elbow, and fasten the vent connector to the vent elbow

    with at least two field--supplied, corrosion--resistant, sheet

    metal screws located 180_ apart.

    NOTE: An accessory flue extension KGAFE0112UPH is

    available to extend from the furnace elbow to outside the furnace

    casing. If flue extension is used, fasten the flue extension to the

    vent elbow with at least two field--supplied, corrosion -- resistant,

    sheet metal screws located 180_ apart. Fasten the vent connector

    to the flue extension with at least two field--supplied, corrosion

    resistant sheet metal screws located 180_ apart.

    2. Vent the furnace with the appropriate connector as shown

    in Fig. 34 --46.

    CUT HAZARD

    Failure to follow this caution may result in personal injury .

    Sheet metal parts may have sharp edges or burrs. Use care

    and wear appropriate protective clothing, safety glasses and

    gloves when handling parts and servicing furnaces.

    CAUTION

    !

    3. Orient the door to determine the correct location of the

    door cutout to be removed.

    4. Use aviation-- type tin snips to remove the correct

    U--shaped cut--out in door.

    NOTE: If this furnace is equipped with knockouts in the door

    for the vent, a number of techniques can be used to remove these

    knockouts as seen in Fig. 47 through 51. The knockout in the

    bottom of the door is unique due to its flanging and is not easily

    removed by first cutting the two tie points at the edge of the door,

    using aviation--type tin snips. (See Fig. 47.) A sharp blow to the

    rounded end of the knockout (See Fig. 48.) will separate more tie

    points and allow the knockout to be pulled loose. (See Fig. 49.)

    Remove all burrs and sharp edges. For the knockouts in the other

    locations on the door (top and sides), tin snips can also be used

    along the door edges; however, the preferred method is to use a

    hammer and screwdriver to strike a sharp blow (See Fig. 50.)

    directly to the knockout tie points or use a hammer in the upper

    left corner of the desired knockout. (See Fig. 51.) Remove all

    burrs and sharp edges.

    BURN HAZARD

    Failure to follow this caution may cause personal injury.

    Hot vent pipe is within reach of small children when

    installed in downflow position. See the following

    instruction.

    CAUTION

    !

    An accessory Vent Guard Kit, KGAVG0101DFG is REQUIRED

    for downflow applications for use where the vent exits through

    the lower portion of the furnace casing door. Refer to the Vent

    Guard Kit Instructions for complete details.

    The horizontal portion of the venting system shall slope upwards

    not less than 1/4 -- in. per linear ft. (21 mm/M) from the furnace to

    the vent and shall be rigidly supported every 5 ft. (2 M) or less

    with metal hangers or straps to ensure there is no movement after

    installation.

    SIDEWALL

    VENTING

    This furnace is not approved for direct sidewall horizontal

    venting.

    In the U.S.: Per section 12.4.3.1 of the NFPA54/ANSI

    Z223.1-- 2006, any listed mechanical venter may be used, when

    approved by the authority having jurisdiction.

    In Canada: Per section 8.24.2 of the CAN/CSA-- B149.1 --05,

    any listed venters may be used, when approved by the authority

    having jurisdiction.

    Select the listed mechanical venter to match the Btuh input of the

    furnace being vented. Follow all manufacturer’ s installation

    requirements for venting and termination included with the listed

    mechanical venter .

    313A

  • Page 31:

    31

    SEE NOTES: 1,2,4,7,8,9

    on the page following

    these figures

    A03208

    Fig. 34 -- Upflow Application-- Vent Elbow Up

    SEE NOTES: 1,2,3,4,7,8,9

    on the pages following

    these figures

    A03209

    Fig. 35 -- Upflow Application-- Vent Elbow Right

    SEE NOTES:1,2,3,4,5,7,8,9

    on the page following

    these figures

    A03210

    Fig. 36 -- Downflow Application--Vent Elbow Up then Left

    SEE NOTES: 1,2,4,5,7,8,9

    on the page following

    these figures

    A03211

    Fig. 37 -- Downflow Application-- Vent Elbow Up

    313A

  • Page 32:

    32

    SEE NOTES: 1,2,4,5,6,7,8,9

    on the page following these figures

    A03207

    Fig. 38 -- Downflow Application--Vent Elbow Left then Up

    SEE NOTES:1,2,3,4,5,7,8,9

    on the page following

    these figures.

    A03212

    Fig. 39 -- Downflow Application-- Vent Elbow Up then Right

    SEE NOTES: 1,2,4,7,8,9 on the page

    following these figures

    A03213

    Fig. 40 -- Horizontal Left Application--Vent Elbow Left

    SEE NOTES: 1,2,4,5,7,8,9 on the page

    following these figures

    A03214

    Fig. 41 -- Horizontal Left Application--Vent Elbow Right

    then Up

    313A

  • Page 33:

    33

    SEE NOTES: 1,2,4,7,8,9 on the page

    following these figures

    A03214

    Fig. 42 -- Horizontal Right Application--Vent Elbow Right

    SEE NOTES: 1,2,4,5,7,8,9 on the page

    following these figures

    A03215

    Fig. 43 -- Horizontal Left Application--Vent Elbow Up

    SEE NOTES: 1,2,4,5,7,8,9 on the page

    following these figures

    A03219

    Fig. 44 -- Horizontal Right Application-- Vent Elbow Left

    then Up

    SEE NOTES: 1,2,4,5,7,8,9 on the page

    following these figures

    A03216

    Fig. 45 -- Horizontal Left Application--Vent Elbow Right

    SEE NOTES: 1,2,4,5,7,8,9

    A02068

    Fig. 46 -- Horizontal Right Application-- Vent Elbow Left

    313A

  • Page 34:

    34

    Venting Notes for Figures 34--46

    1. For common vent, vent connector sizing and vent

    material: United States----use the NFGC Canada----use the

    CAN/CSA--B149.1 --05

    2. Immediately increase to 5-- inch (127 mm) or 6 --inch (152

    mm) vent connector outside furnace casing when 5--inch

    (127 mm) vent connector is required, refer to Note 1

    above.

    3. Side outlet vent for upflow and downflow installations

    must use Type B vent immediately after exiting the

    furnace, except when KGAVG0101DFG, Downflow Vent

    Guard Kit, is used in the downflow position.

    4. Type-- B vent where required, refer to Note 1 above.

    5. Four--inch single--wall (26 ga. min.) vent must be used

    inside furnace casing and when the KGAVG0101DFG

    Downflow Vent Guard Kit is used external to the furnace.

    6. Accessory Downflow Vent Guard Kit, KGAVG0101DFG

    required in downflow installations with lower vent

    configuration.

    7. Chimney Adapter Kit may be required for exterior

    masonry chimney applications. Refer to Chimney Adapter

    Kit, KGACA02014FC or KGACA02015FC, for sizing

    and complete application details.

    8. Secure vent connector to furnace elbow with (2)

    corrosion--resistant sheet metal screws, spaced

    approximately 180_ apart.

    9. Secure all other single wall vent c onnector joints with (3)

    corrosion resistant screws spaced approximately 120_

    apart. Secure T ype--B vent connectors per vent connector

    manufacturer’s recommendations.

    A04127

    Fig. 47 -- Using Tin Snips to Cut Tie Points

    313A

  • Page 35:

    35

    A04128

    Fig. 48 -- Rounded End of Knockout

    A04129

    Fig. 49 -- Knockout Pulled Loose

    A04130

    Fig. 50 -- Hammer a nd Screwdriver Used for Knockout

    A04131

    Fig. 51 -- Remove Knockout with Hammer

    313A

  • Page 36:

    36

    START--UP, ADJUSTMENT, AND SAFETY

    CHECK

    General

    FIRE HAZARD

    Failure to follow this warning could result in personal

    injury, death and/or property damage.

    This furnace is equipped with manual reset limit switches in

    the gas control area. The switches open and shut off power

    to the gas valve if a flame rollout or overheating condition

    occurs in the gas control area. DO NOT bypass the

    switches. Correct inadequate combustion air supply

    problem before resetting the switches.

    !

    WARNING

    CUT HAZARD

    Failure to follow this caution may result in personal injury .

    Sheet metal parts may have sharp edges or burrs. Use care

    and wear appropriate protective clothing, safety glasses and

    gloves when handling parts and servicing furnaces.

    CAUTION

    !

    1. Maintain 115--v wiring and ground. Improper polarity will

    result in rapid flashing LED and no furnace operation.

    2. Make thermostat wire connections at the 24--v terminal

    block on the furnace control. Failure to make proper

    connections will result in improper operation. (See Fig.

    25.)

    3. Gas supply pressure to the furnace must be greater than

    4.5--in. wc (0.16 psig ) but not exceed 14--in. wc (0.5

    psig).

    4. Check all manual-- reset switches for continuity.

    5. Install blower compartment door. Door must be in place to

    operate furnace.

    6. Replace outer door.

    Start--Up Procedur

    es

    FIRE AND EXPLOSION HAZARD

    Failure to follow this warning could cause personal injury,

    death and/or property damage.

    Never test for gas leaks with an open flame. Use a

    commercially available soap solution made specifically for

    the detection of leaks to check all connections.

    !

    WARNING

    1. Purge gas lines after all connections have been made.

    2. Check gas lines for leaks.

    3. To Begin Component Self--Test:

    Remove blower access door. Disconnect the thermostat R

    lead from the furnace control board. Manually close the

    blower door switch closed. Short (jumper) the COM --24v

    termin al on control to the TEST/TWIN 3/16--inch quick

    connect terminal on control until LED goes out

    (approximately 2 sec). Gas valve and humidifier will not

    be turned on. (See Fig. 24.)

    ELECTRICAL SHOCK HAZARD

    Failure to follow this warning could result in personal

    injury, or death.

    Blower access door switch opens 115--v power to control.

    No component operation can occur unless switch is closed.

    Caution must be taken when manually closing this switch

    for service purposes.

    !

    WARNING

    NOTE: The furnace control allows all components, except the

    gas valve, to be run for short period of time. This feature helps

    diagnose a system problem in case of a component failure.

    Component test feature will not operate if any thermostat signal is

    present at the control.

    Component test sequence is as follows:

    Refer to service label attached to furnace or see Fig. 55.

    a. LED will display previous status code 4 times.

    b. Inducer motor starts and continues to run until Step f of

    component test sequence.

    c. Hot surface igniter is energized for 15 sec., then off.

    d. Blower motor operates on HEAT speed for 10 sec.

    e. Blower motor operates on COOL speed for 10 sec.

    f. Inducer motor stops.

    g. Reconnect R lead to furnace control board, release blower

    door switch and re--install blower door.

    4. Operate furnace per instruction on door.

    5. Verify furnace shut down by lowering thermostat setting

    below room temperature.

    6. Verify furnace restarts by raising thermostat setting above

    room temperature.

    Adjustments

    FIRE HAZARD

    Failure to follow this warning could result in injury, death

    and/or property damage.

    DO NOT bottom out gas valve regulator adjusting screw.

    This can result in unregulated manifold pressure and result in

    excess overfire and heat exchanger failures.

    !

    WARNING

    FURNACE DAMAGE HAZARD

    Failure to follow this caution may result in reduced furnace

    life.

    DO NOT redrill orifices. Improper drilling (burrs,

    out-- of--round holes, etc.) can cause excessive burner noise

    and misdirection of burner flames. This can result in flame

    impingement of heat exchangers, causing failures. (See Fig.

    53.)

    CAUTION

    !

    Furnace gas input rate on rating plate is for installations at

    altitudes up to 2000 ft. (610 M). Furnace input rate must be

    within +/-- 2 percent of furnace rating plate input. For altitudes

    above 5500 ft. (1676 M), a field--supplied high altitude pressure

    switch is required.

    1. Determine the correct gas input rate.

    In the U.S.A.:

    313A

  • Page 37:

    37

    The input rating for altitudes above 2,000 ft. (610 M) must

    be reduced by 4 percent for each 1,000 ft. (305 M) above

    sea level. For installations below 2000 ft. (610 M), refer to

    the unit rating plate. For installations above 2000 ft. (610

    M), multiply the input on the rating plate by the de--rate

    multiplier in Table 8 for the correct input rate.

    In Canada:

    The input rating must be derated by 10 percent for

    altitudes of 2,000 ft. (610 M) to 4,500 ft. (1372 M) above

    sea level by an authorized Gas Conversion Station or

    Dealer. To determine correct input rate for altitude, see

    example 1 and use 0.90 as derate multiplier factor .

    EXAMPLE 1:

    88,000 BTUH INPUT FURNACE INSTALLED AT 4300

    FT. (1310 M)

    Furnace Input

    Rate at Sea

    Level

    X Derate

    Multiplier

    Factor

    0.90

    = Furnace Input

    Rate at

    Installation

    Altitude

    88,000 X = 79,200

    2. Determine the correct orifice and manifold pressure

    adjustment. There are two different orifice and manifold

    adjustment tables. All models in all positions, except Low

    NOx models in downflow or horizontal positions, use

    Table 13 (22,000 Btuh/Burner).

    Low NOx models in the downflow or horizontal positions

    must use Table 14 (21,000 Btuh/Burner). See input listed

    on rating plate.

    a. Obtain average yearly gas heat value (at installed altitude)

    from local gas supplier.

    b. Obtain average yearly gas specific gravity from local gas

    supplier.

    c. Find installation altitude in Table 13 or 14.

    d. Find closest natural gas heat value and specific gravity

    in Table 13 or 14.

    e. Follow heat value and specific gravity lines to point of

    intersection to find orifice size and manifold pressure

    settings for proper operation.

    f. Check and verify burner orifice size in furnace. NEVER

    ASSUME ORIFICE SIZE. ALWAYS CHECK AND

    VERIFY.

    g. Replace orifice with correct size if required by Table 10,

    12, 13, and 14. Use only factory--supplied orifices. See

    EXAMPLE 2.

    Caution!! For the following applications, use the minimum vertical vent heights as specified below. For all other applications,

    follow exclusively the National Fuel Gas Code.

    FURNACE

    ORIENTATION

    VENT ORIENTATION

    FURNACE INPUT

    (BTUH/HR)

    MIN. VENT

    DIAMETER

    IN (MM)*

    MIN. VERTICAL VENT

    HEIGHT

    FT. (M)**

    Downflow Vent elbow left, then up Fig. 38 132,000 5 (127 ) 12 (4)

    Horizontal Left Vent elbow right, then up Fig. 41 132,000 5 (127 ) 7(2)

    Horizontal Left Vent elbow right Fig. 42 132,000 5 (127 ) 7(2)

    NOTE: All vent configurations must also meet National Fuel Gas Code venting requirements NFGC

    *4 in. (102 mm) inside casing or vent guard

    **Including 4 in. (102 mm) vent section(s)

    Table 10 – Altitude Derate Multiplier for U.S.A.

    ALTITUDE

    (FT. / M)

    PERCENT

    OF

    DERATE

    DERATE

    MULTIPLIER

    FACTOR*

    0–2000 (0--- 610) 0 1.00

    2001–3000 (610--- 914) 8–12 0.90

    3001–4000 (914--- 1219) 12–16 0.86

    4001–5000 (1219--- 1524) 16–20 0.82

    5001–6000 (1524--- 1829) 20–24 0.78

    6001–7000 (1829--- 2134) 24–28 0.74

    7001–8000 (2134--- 2438) 28–32 0.70

    8001–9000 (2438--- 2743) 32–36 0.66

    9001–10,000 (2743--- 3048) 36–40 0.62

    * D erate multiplier f actors are based on midpoint altitude for altitu de

    range.

    3. Adjust manifold pressure to obtain correct input rate.

    a. Turn gas valve ON/OFF switch to OFF.

    b. Remove manifold pressure tap plug from gas valve. (See

    Fig. 52.)

    c. Connect a water column manometer or similar device to

    manifold pressure tap.

    d. Turn gas valv e ON/OFF switch to ON.

    e. Manually close blower door switch.

    f. Set thermostat to call for heat.

    g. Remove regulator seal cap and turn regulator adjusting

    screw counterclockwise (out) to decrease input rate of

    clockwise (in) to increase input rate.

    EXAMPLE 2: (0 to 2000 ft. (0 to 610 M) altitude)

    For 22,000 Btuh per burner application use Table 13.

    Heating value = 1000 Btuh/cu ft.

    Specific gravity = 0.62

    Therefore: Orifice No. 43*

    Manifold pressure: 3.7 --in. wc

    *Furnace is shipped with No. 43 orifices.

    In this example all main burner orifices are the correct

    size and do not need to be changed to obtain proper

    input rate.

    h. Install regulator seal cap.

    i. Leave manometer or similar device connected and

    proceed to Step 4.

    NOTE: DO NOT set manifold pressure less than 3.2--in wc or

    more than 3.8--in. wc for natural gas at sea level. If manifold

    pressure is outside this range, change main burner orifices. Refer

    to Table 10, 12, 13, and 14.

    NOTE: If orifice hole appears damaged or it is suspected to have

    been redrilled, check orifice hole with a numbered drill bit of

    correct size. Never redrill an orifice. A burr--free and squarely

    aligned orifice hole is essential for proper flame characteristics.

    4. Verify natural gas input rate by clocking meter.

    NOTE: Gas valve regulator adjustment cap must be in place for

    proper input to be clocked.

    a. Turn off all other gas appliances and pilots served by the

    meter.

    b. Run furnace for 3 minutes in heating operation.

    313A

  • Page 38:

    38

    c. Measure time (in sec) for gas meter to complete 1

    revolution and note reading. The 2 or 5 cubic feet dial

    provides a more accurate measurement of gas flow.

    d. Refer to Table 12 for cubic ft. of gas per hr.

    e. Multiply gas rate (cu ft./hr) by heating value (Btuh/cu ft.)

    to obtain input.

    If clocked rate does not match required input from Step 1,

    increase manifold pressure to increase input or decrease manifold

    pressure to decrease input. Repeat steps b through e until correct

    input is achieved. Reinstall regulator seal cap on gas valve.

    5. Set temperature rise. The furnace must operate within the

    temperature rise ranges specified on the furnace rating

    plate. Do not exceed temperature rise range specified on

    unit rating plate. Determine the temperature rise as

    follows:

    NOTE: Blower access door must be installed when taking

    temperature rise reading. Leaving blower access door off will

    result in incorrect temperature measurements.

    ELECTRICAL SHOCK HAZARD

    Failure to follow this warning could result in personal injury

    or death.

    Disconnect 115--v electrical power before changing speed

    tap.

    !

    WARNING

    a. Place thermometers in return and supply ducts as close

    to furnace as possible. Be sure thermometers do not see

    radiant heat from heat exchangers. Radiant heat affects

    temperature rise readings. This practice is particularly

    important with straight--run ducts.

    b. When thermometer readings stabilize, subtract return--air

    temperaturefromsupply-- airtemperatureto determine air

    temperature rise.

    NOTE: Blower access door must be installed for proper

    temperature rise measurement.

    NOTE: If the temperature rise is outside this range, first check:

    (1.) Gas input for heating operation.

    (2.) Derate for altitude if applicable.

    (3.) Return and supply ducts for excessive restrictions

    causing static pressures greater than 0.50--in. wc.

    (4.) Dirty filter.

    c. Reinstall blower access door if removed.

    d. Turn gas valv e ON/OFF switch to ON.

    e. Adjust air temperature rise by adjusting blower speed.

    Increase blower speed to reduce temperature rise.

    Decrease blower speed to increase temperature rise

    f. Turn thermostat down below room temperature and

    remove blower access door.

    g. To change motor speed selection for heating, remove

    blower motor lead from control HEAT terminal (See Fig.

    24.) Select desired blower motor speed lead from one of

    the other terminals and relocate it to the HEAT terminal

    (See Table 11 for lead color identification). Reconnect

    original lead to SPARE terminal.

    h. Repeat steps a through e.

    i. When correct input rate and temperature rise is achieved,

    turn gas valve ON/OFF switch to OFF.

    j. Remove manometer or similar d evice from gas valve.

    k. Reinstall manifold pressure tap plug in gas valve.

    A06666

    Fig. 52 -- Gas Control Valve

    BURNER

    ORIFICE

    A93059

    Fig. 53 -- Orifice Hole

    FIRE HAZARD

    Failure to follow this warning could result in personal

    injury, death, and/or property damage.

    Reinstall manifold pressure tap plug in gas valve to prevent

    gas leak.

    !

    WARNING

    313A

  • Page 39:

    39

    Table 11 – Speed Selection

    COLOR SPEED AS SHIPPED

    Gray 5 COOL

    Yellow 4 SPARE

    Blue 3 HEAT

    Orange 2 SPARE

    Red 1* CONT FAN

    * C o n t in u o u s --- b l o w e r s p e e d --- a s s h ip p e d d e f a u l t

    FURNACE OVERHEATING HAZARD

    Failure to follow this caution may result in reduced furnace

    life.

    Recheck temperature rise. It must be within limits specified

    on the rating plate. Recommended operation is at the

    mid --point of rise range or slightly above.

    CAUTION

    !

    6. Set thermostat heat anticipator.

    a. Mechanical thermostat -- Set thermostat heat anticipator

    to match the amp. draw of the electrical components in

    the R--W circuit. Accurate amp. draw readings can be

    obtained at the wires normally connected to thermostat

    subbase terminals, R and W. The thermostat anticipator

    should NOT be in the circuit while measuring current.

    (1.) Remove thermostat from subbase or from wall.

    (2.) Connect an amp. meter as shown in Fig. 54 across

    the R and W subbase terminals or R and W wires at

    wall.

    (3.) Record amp. draw across terminals when furnace is

    in heating and after blower starts.

    (4.) Set heat anticipator on thermostat per thermostat

    instructions and install on subbase or wall.

    b. Electronic thermostat: Set cycle rate for 4 cycles per hr.

    7. Adjust blower off delay The blower off delay has 4

    adjustable settings from 90 sec to 180 sec. The blower off

    delay jumpers are located on the furnace control board.

    (See Fig. 24.)

    To change the blower off delay setting, move the jumper

    from one set of pins on the control to the pins used for the

    selected blower of f delay . Factory off delay setting is 120

    sec.

    8. Set airflow CFM for cooling

    Select the desired blower motor speed lead for cooling

    airflow. See Table 5--Air Delivery--CFM (With Filter). See

    Table 11 for lead color identification.

    Check Safety Contr

    ols

    The flame sensor, gas valve, and pressure switch were all checked

    in the Start--up procedure section as part of normal operation.

    1. Check Main Limit Switch(es)

    This control shuts off combustion control system and

    energizes air--circulating blower motor , if furnace

    overheats. By using this method to check limit control, it

    can be established that limit is functioning properly and

    will operate if there is a restricted duct system or motor

    failure. If limit control does not function during this test,

    cause must be determined and corrected.

    a. Run furnace for at least 5 minutes.

    b. Gradually block off return air with a piece of cardboard

    or sheet metal until the limit trips.

    c. Unblock return air to permit normal circulation.

    d. Burners will re --light when furnace cools down.

    2. Check draft safeguard switch.

    The purpose of this control is to cause the safe shutdown

    of the furnace during certain blocked vent conditions.

    R Y W G

    10 TURNS

    THERMOSTAT SUBBASE

    TERMINALS WITH

    THERMOSTAT REMOVED

    (ANITICIPATOR, CLOCK, ETC.,

    MUST BE OUT OF CIRCUIT.)

    HOOK-AROUND

    AMMETER

    EXAMPLE:

    5.0 AMPS ON AMMETER

    10 TURNS AROUND JAWS

    =

    0.5 AMPS FOR THERMOSTAT

    ANTICIPATOR SETTING

    FROM UNIT 24-V

    CONTROL TERMINALS

    A96316

    Fig. 54 -- Amp. Draw Check with Ammeter

    a. Verify vent pipe is cool to the touch.

    b. Disconnect power to furnace and remove vent connector

    from furnace vent elbow.

    c. Restore power to furnace and set room thermostat above

    room temperature.

    d. After normal start-- up, allow furnace to operate for 2

    minutes, then block vent elbow in furnace 80 percent of

    vent area with a piece of flat sheet metal.

    e. Furnace should cycle off within 2 minutes. Ifgasdoesnot

    shut off within 2 minutes, determine reason draft

    safeguard switch did not function properly and correct

    condition.

    f. Remove blockage from furnace vent elbow.

    g. Switch will auto--reset when it cools.

    h. Re--install vent connector.

    NOTE: Should switch remain open longer than 3 minutes,

    furnace control board will lockout the furnace for 3 hours. To

    reset furnace control board, turn thermostat below room

    temperature or from HEAT to OFF and turn 115v power OFF,

    then back ON.

    3. Check Pressure Switch

    This control proves operation of the draft inducer blower.

    a. Turn off 115--v power to furnace.

    b. Disconnect inducer motor lead wires from wire harness.

    c. Turn on 115--v power to furnace.

    d. Set thermostat to “call for heat” and wait 1 minute. When

    pressure switch is functioning properly, hot surface

    igniter should NOT glow and control diagnostic light

    flashes a status code 32. If hot surface igniter glows when

    inducer motor is disconnected, shut down furnace

    immediately.

    e. Determine reason pressure switch did not function

    properly and correct condition.

    f. Turn off 115--v power to furnace.

    g. Reconnect inducer motor wires, replace outer door, and

    turn on 115--v power.

    h. Blower will run for 90 sec before beginning the call

    forheat again.

    i. Furnace should ignite normally.

    313A

  • Page 40:

    40

    Table 12 – Gas Rate (Cu Ft./Hr.)

    SECONDS

    FOR 1 REVOLUTION

    SIZE OF TEST DIAL

    SECONDS

    FOR 1 REVOLUTION

    SIZE OF TEST DIAL

    1

    Cu Ft.

    2CuFt. 5CuFt. 1CuFt. 2CuFt. 5CuFt.

    10 360 720 1800 50 72 144 360

    11 327 655 1636 51 71 141 355

    12 300 600 1500 52 69 138 346

    13 277 555 1385 53 68 136 340

    14 257 514 1286 54 67 133 333

    15 240 480 1200 55 65 131 327

    16 225 450 1125 56 64 129 321

    17 212 424 1059 57 63 126 316

    18 200 400 1000 58 62 124 310

    19 189 379 947 59 61 122 305

    20 180 360 900 60 60 120 300

    21 171 343 857 62 58 116 290

    22 164 327 818 64 56 112 281

    23 157 313 783 66 54 109 273

    24 150 300 750 68 53 106 265

    25 144 288 720 70 51 103 257

    26 138 277 692 72 50 100 250

    27 133 267 667 74 48 97 243

    28 129 257 643 76 47 95 237

    29 124 248 621 78 46 92 231

    30 120 240 600 80 45 90 225

    31 116 232 581 82 44 88 220

    32 113 225 563 84 43 86 214

    33 109 218 545 86 42 84 209

    34 106 212 529 88 41 82 205

    35 103 206 514 90 40 80 200

    36 100 200 500 92 39 78 196

    37 97 195 486 94 38 76 192

    38 95 189 474 96 38 75 188

    39 92 185 462 98 37 74 184

    40 90 180 450 100 36 72 180

    41 88 176 439 102 35 71 178

    42 86 172 429 104 35 69 173

    43 84 167 419 106 34 68 170

    44 82 164 409 108 33 67 167

    45 80 160 400 110 33 65 164

    46 78 157 391 112 32 64 161

    47 76 153 383 116 31 62 155

    48 75 150 375 120 30 60 150

    49 73 147 367

    Checklist

    1. Put away tools and instruments. Clean up debris.

    2. Verify that blower OFF--DELAY time is selected as

    desired.

    3. Verify that blower and burner access doors are properly

    installed.

    4. Cycle test furnace with room thermostat.

    5. Check operation of accessories per manufacturer’s

    instructions.

    6. Review User’s Guide with owner.

    7. Attach literature packet to furnace

    .

    313A

  • Page 41:

    41

    Table 13 – Orifice Size* and Manifold Pressure (In. wc) for Gas Input Rate

    A08220

    313A

  • Page 42:

    42

    Table 13 -- Orifice Size* and Manifold Pressure (In. wc) for Gas Input Rate (CONT)

    A08220A

    313A

  • Page 43:

    43

    SERVICE AND MAINTENANCE

    PROCEDURES

    FIRE, INJURY, OR DEATH HAZARD

    Failure to follow this warning could result in personal

    injury, death and/or property damage.

    The ability to properly perform maintenance on this

    equipment requires certain knowledge, mechanical skills,

    tools, and equipment. If you do not possess these, do not

    attempt to perform any maintenance on this equipment

    other than those procedures recommended in the User’s

    Manual.

    !

    WARNING

    ELECTRICAL SHOCK, FIRE OR EXPLOSION

    HAZARD

    Failure to follow this warning could result in personal

    injury or death, or property damage.

    Before servicing, disconnect all electrical power to furnace.

    Verify proper operation after servicing.

    !

    WARNING

    ELECTRICAL OPERATION HAZARD

    Failure to follow this caution may result in improper

    furnace operation or failure of furnace.

    Label all wires prior to disconnection when servicing

    controls. Wiring errors can cause improper and dangerous

    operation.

    CAUTION

    !

    INTRODUCTION

    GENERAL

    These instructions are written as if the furnace is installed in an

    upflow application. An upflow furnace application is where the

    blower is located below the combustion and controls section of

    the furnace, and conditioned air is discharged upward. Since this

    furnace can be installed in any of the 4 positions shown in Fig. 4,

    you must revise your orientation to component location

    accordingly.

    ELECTRICAL CONTROLS AND

    WIRING

    ELECTRICAL SHOCK HAZARD

    Failure to follow this warning could result in personal

    injury or death.

    There may be more than one electrical supply to the

    furnace. Check accessories and cooling unit for additional

    electrical supplies that must be shut off during furnace

    servicing.

    CAUTION

    !

    The electrical ground and polarity for 115--v wiring must be

    properly maintained. Refer to Fig. 25 for field wiring information

    and to Fig. 59 for furnace wiring information.

    NOTE: If the polarity is not co rrect, the STATUS LED on the

    control will flash rapidly and prevent the furnace from heating.

    The control system also requires an earth ground for proper

    operation of the control and flame--sensing electrode.

    The 24--v circuit contains an automotive--type, 3 --amp.. fuse

    located on the control. (See Fig. 24.) Any shorts of the 24 --v

    wiring during installation, service, or maintenance will cause this

    fuse to blow . If fuse replacement is required, use ONLY a 3--amp.

    fuse. The control LED will display status code 24 when fuse

    needs to be replaced.

    Proper instrumentation is required to service electrical controls.

    The control in this furnace is equipped with a Status Code LED

    (Light--Emitting Diode) to aid in installation, servicing, and

    troubleshooting. It can be viewed through the sight glass in

    blower access door. The furnace control LED is either ON

    continuously, rapid flashing, or a code composed of 2 digits. The

    first digit is the number of short flashes, the second digit is the

    number of long flashes.

    For an explanation of status codes, refer to service label located

    on blower access door or Fig. 55 and the troubleshooting guide

    which can be obtained from your distributor.

    See Fig. 60, a brief Troubleshooting Guide.

    For Controls With an Amber

    LED

    The stored status code will not be erased from the control

    memory, if 115-- or 24 --v power is interrupted.

    1. To retrieve status code, proceed with the following:

    NOTE: NO thermostat signal may be present at control, and all

    blower--OFF delays must be completed.

    a. Leave 115--v power to furnace turned on.

    b. Remove outer access door.

    c. Look into blower access door sight glass for current LED

    status. Removing blower access door will open blower

    access door switch and terminate 115--v power to control

    so that status code is not displayed.

    d. BRIEFLY remove insulated terminal wire from the draft

    safeguard (DSS) switch until LED goes out, then

    reconnect it.

    NOTE: If wire to LS or DSS is disconnected longer than 4 sec,

    main blower starts, and retrieval request is ignored.

    2. When above items have been completed, the LED flashes

    status code 4 times. Record this status code for further

    troubleshooting.

    3. Check LED status. If no previous faults in history, control

    will flash status code 11.

    313A

  • Page 44:

    44

    Table 14 – Orifice Size* And Manifold Pressure (In. wc) For Gas Input Rate

    A08221

    313A

  • Page 45:

    45

    Table 14-- Orifice Size* And Manifold Pressure (In. wc) For Gas Input Rate (CONT)

    A08221A

    To initiate the component test sequence, shut OFF the room thermostat or disconnect the "R"

    thermostat lead. Briefly short the TEST/TWIN terminal to the "Com 24V" terminal. Status LED

    will flash code and then turn ON the inducer motor. The inducer motor will run for the entire

    component test. The hot surface ignitor, blower motor fan speed (on AMBER LED boards

    only) blower motor-heat speed, and blower motor-cool speed will be turned ON for 10-15

    seconds each. Gas V

    alve and Humidifier will not be turned on.

    CONTINUOUS OFF - Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2.

    CONTINUOUS ON - Control has 24VAC power.

    RAPID FLASHING - Line voltage (115VAC) polarity reversed. If twinned, refer to twinning kit instructions.

    LED CODE

    STATUS

    11 NO PREVIOUS CODE - Stored status code is erased automatically after 72 hours. On

    RED LED boards stored status codes can also be erased when power

    (115 VAC or 24 VAC) to control is interrupted.

    12 BLOWER ON AFTER POWER UP (115 VAC or 24 VAC) -Blower runs for 90 seconds,

    if unit is powered up during a call for heat (R-W closed) or R-W opens during blower

    on-delay.

    13 LIMIT CIRCUIT LOCKOUT - Lockout occurs if the limit, draft safegua

    rd, flame rollout, or

    blocked vent switch (if used) i s open longer than 3 minutes.

    - Control wi ll auto reset after three hours. - Refer to #33.

    14 IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to #34.

    21 GAS HEATING LOCKOUT - Control will NOT auto reset.

    Check for: - Mis-wired gas valve -Defective control (valve relay)

    22 ABNORMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is de-

    energized. Inducer will run until f

    ault is cleared. Check for: - Leaky gas valve

    - Stuck-open gas valve

    23 PRESSURE SWITCH DID NOT OPEN Check for:

    - Obstructed pressure tubing. - Pressure switch stuck closed.

    24 SECONDARY VOLTAGE FUSE IS OPEN Check for:

    - Short circuit in secondary voltage (24VAC) wiring.

    If status code recall is needed, briefly remove then reconnect one main limit wire to display stored status code. On RED LED boards do not remove power or blower door before initia ting status code recall. After

    status code recall is completed component test will occur.

    327596-101 REV. B

    31 PRESSURE SWITCH DID NOT CLOSE OR REOPENED - If open longer than five minutes,

    inducer shuts off for 15 minutes before retry. Check for: - Excessive wind

    - Proper vent sizing - Defective inducer motor

    - Low inducer voltage (115VAC) - Defective pressure switch

    - Inadequate combustion air supply - Disconnected or obstructed pressure tubing

    - Low inlet gas pressure (if LGPS used) - Restricted vent

    If it opens during blower on-delay period, blower will come on for the selected blower

    off-delay.

    33 LIMIT CIRCUIT FAULT - In

    dicates a limit, draft safeguard, flame rollout, or blocked vent

    switch (if used) is open. Blower will run for 4 minutes or until open switch remakes

    whichever is longer. If open longer than 3 minutes, code changes to lockout #13.

    If open less than 3 minutes status code #33 continues to flash until blower shuts off.

    Flame rollout switch and BVSS require manual reset. Check for: - Restri

    cted vent

    - Proper vent sizing - Loose blower wheel. - Excessive wind

    - Dirty filter or restricted duct system.

    - Defective blower motor or capacitor. - Defective switch or connections.

    - Inadequate combustion air supply (Flame Roll-out Switch open).

    34 IGNITION PROVING FAILURE - Control will try three more times before lockout #14

    occurs. If flame signal lost during blower on-delay period, blower will come on for the

    selected blower off-delay. Check for: - Flame se

    nsor must not be grounded

    - Oxide buildup on flame sensor (clean with fine steel wool).

    - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal).

    - Gas valve defective or gas valve turned off - Manual valve shut-off

    - Defective Hot Surface Ignitor - Control ground continuity

    - Low inlet gas pressure - Inadequate flame c

    arryover or rough ignition

    - Green/Yellow wire MUST be connected to furnace sheet metal

    45 CONTROL CIRCUITRY LOCKOUT Auto-reset after one hour lockout due to;

    - Gas valve relay stuck open - Flame sense circuit failure - Software check error

    Reset power to clear lockout. Replace control if status code repeats.

    SERVICE

    COMPONENT TEST

    EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY THE NUMBER OF LONG FLASHES.

    A04223

    Fig. 55 -- Service Label

    313A

  • Page 46:

    46

    CARE AND

    MAINTENANCE

    FIRE OR EXPLOSION HAZARD

    Failure to follow this warning could result in personal

    injury, death and/or property damage.

    Never store anything on, near, or in contact with the

    furnace, such as:

    1. Spray or aerosol cans, rags, brooms, dust mops,

    vacuum cleaners, or other cleaning tools.

    2. Soap powders, bleaches, waxes or other cleaning

    compounds, plastic or plastic containers, gasoline,

    kerosene, cigarette lighter fluid, dry cleaning fluids,

    or other volatile fluids.

    3. Paint thinners and other painting compounds, paper

    bags, or other paper products.

    !

    WARNING

    For continuing high performance and to minimize possible

    equipment failure, periodic maintenance must be performed on

    this equipment. Consult your local dealer about proper frequency

    of maintenance and the availability of a maintenance contract.

    ELECTRICAL SHOCK AND FIRE HAZARD

    Failure to follow this warning could result in personal

    injury, death or property damage.

    Turn off the gas and electrical supplies to the unit before

    performing any maintenance or service. Follow the

    operating instructions on the label attached to the

    furnace.

    !

    WARNING

    CARBON MONOXIDE POISONING AND

    FIRE HAZARD

    Failure to follow this warning could result in personal

    injury, death and/or property damage.

    Never operate unit without a filter or with filter access door

    removed.

    !

    WARNING

    CUT HAZARD

    Failure to follow this caution may result in personal injury .

    Sheet metal parts may have sharp edges or burrs. Use care

    and wear appropriate protective clothing, safety glasses and

    gloves when handling parts and servicing furnaces.

    CAUTION

    !

    The minimum maintenance on this furnace is as follows:

    1. Check and clean/replace air filter each month or more

    frequently if required. Replace if torn.

    2. Check blower motor and wheel for cleanliness each

    heating and cooling season. Clean as necessary.

    3. Check electrical connections for tightness and controls for

    proper operation each heating season. Service as

    necessary.

    4. Inspect burner compartment before each heating season

    for rust, corrosion, soot or excessive dust. If necessary,

    have furnace and burner serviced by a qualified service

    agency.

    5. Inspect the vent pipe/vent system before each heating

    season for rust, corrosion, water leakage, sagging pipes or

    broken fittings. Have vent pipes/vent system serviced by a

    qualified service agency.

    6. Inspect any accessories attached to the furnace such as a

    humidifier or electronic air cleaner. Perform any service or

    maintenance to the accessories as recommended in the

    accessory instructions.

    CLEANING AND/OR REPLACING AIR F IL

    TER

    The air filter arrangement will vary depending on the application.

    The filter is exterior to the furnace casing.

    NOTE: If the filter has an airflow direction arrow , the arrow

    must point towards the blower.

    Table 15 – Filter Size Information (In. / mm)

    FURNACE

    CASING

    WIDTH

    In. (mm)

    FILTER SIZE (In. / mm)

    FIL TER TYPE

    Side Return Bottom Return

    14---1/2

    (368)

    16 x 25 x 3/4

    (406 x 635 x 19)

    14 x 25 x 3/4

    (356 x 635 x 19)

    Washable*

    17---1/2

    (445)

    16 X 25 X 3/4

    (406 x 635 x 19)

    16 X 25 X 3/4

    (406 x 635 x 19)

    Washable*

    21 (533)

    16 x 25 x 3/4

    (406 x 635 x 19)

    20 X 25 X 3/4

    (508 x 635 x 19)

    Washable*

    24 (610)

    16 x 25 x 3/4

    (406 x 635 x 19)

    24 X 25 X 3/4

    (610 x 635 x 19)

    Washable*

    * Recommended

    Media cabinet filter procedures :

    NOTE: Media cabinet is included with single--stage deluxe

    furnace.

    1. Turn off electrical supply to furnace before removing filter

    access door.

    2. Remove filter cabinet door.

    3. Slide filter out of cabinet.

    4. If equipped with permanent, washable 3/4 -- in. (19 mm) fil-

    ter, clean filter by spraying cold tap water through filter in

    opposite direction of airflow. Rinse filter and let dry.

    Oiling or coating of the filter is not recommended. See

    Table 15 for size information.

    5. If equipped with factory--specified disposable media filter,

    replace only with media filter having the same part

    number and size. For expandable replacement media, refer

    to the instructions included with the replacement media. If

    equipped with accessory KGAFR0301ALL external filter

    rack, See Table 15.

    6. Slide filter into cabinet.

    7. Replace filter cabinet door.

    8. Turn on electrical supply to furnace.

    BLOWER MOTOR AND

    WHEEL

    ELECTRICAL SHOCK HAZARD

    Failure to follow this warning could result in personal injury

    or death.

    Blower access door switch opens 115--v power to control.

    No component operation can occur unless switch is closed.

    Caution must be taken when manually closing this switch

    for service purposes.

    !

    WARNING

    313A

  • Page 47:

    47

    NOTE: The blower wheel should not be dropped or bent as

    balance will be affected. The following steps should be performed

    by a qualified service agency.

    To ensure long life and high efficiency, clean accumulated dirt

    and grease from blower wheel and motor annually.

    The inducer and blower motors are pre-- lubricated and require no

    additional lubrication. These motors can be identified by the

    absence of oil ports on each end of the motor .

    Clean blower motor and wheel as follows:

    1. Turn off electrical supply to furnace.

    2. Loosen the thumbscrew on outer door and remove outer

    door.

    3. For downflow or horizontal furnaces having vent pipes

    within the furnace that pass in front of the blower access

    door:

    a. Disconnect vent connector from furnace vent elbow.

    b. Disconnect and remove short piece of vent pipe from

    within furnace.

    4. Remove two screws from blower access door and remove

    blower access door.

    5. Disconnect both harness connectors from blower motor

    instead of at the circuit board. This reduces the chances of

    a miswire when reconnecting wiring. The connectors are

    polarized to prevent connection in the wrong orientation.

    6. Remove two screws holding control box to blower shelf.

    7. Hang control box from front of furnace casing and away

    from blower compartment.

    8. Remove two screws holding blower assembly to blower

    deck and slide blower assembly out of furnace.

    9. Clean blower wheel and motor using a vacuum with soft

    brush attachment. Blower wheel blades may be cleaned

    with a small paint or flux brush. Do not remove or disturb

    balance weights (clips) on blower wheel blades.

    10. Vacuum any loose dust from blower housing, wheel and

    motor.

    11. If a greasy residue is present on blower wheel, remove

    wheel from the blower housing and wash it with an

    appropriate degreaser. To remove wheel:

    NOTE: Before disassembly, mark blower motor, and blower

    housing so motor and each arm is positioned at the same location

    during reassembly.

    a. Disconnectpower chokewires (ifused) and ground wire

    attached to blower housing.

    b. Remove screws securing cutoff plate and remove cutoff

    plate from housing.

    c. Loosen set screw holding blower wheel on motor shaft

    (160+/-- 20 in.-- lb. when reassembling).

    d. Remove bolts holding motor to blower housing and slide

    motor out of wheel (40+/--10 in.-- lb. when reassembling).

    e. Remove blower wheel from housing.

    f. Clean wheel and housing.

    12. Reassemble motor and blower by reversing steps 11f

    through 11a, finishing with 11a. Be sure to reattach

    ground wire to the blower housing.

    13. Verify that blower wheel is centered in blower housing

    and set screw contacts the flat portion of the motor shaft.

    Loosen set screw on blower wheel and reposition if

    necessary.

    14. Spin the blower wheel by hand to verify that the wheel

    does not rub on the housing.

    15. Reinstall blower assembly in furnace.

    16. Reinstall control box assembly in furnace.

    UNIT DAMAGE HAZARD

    Failure to follow this caution may result in shortened heat

    exchanger life.

    Heating fan speed(s) MUST be adjusted to provide proper

    air temperature rise as specified on the rating plate.

    Recommended operation is at the midpoint of the rise range

    or slightly above. Refer to “SET TEMPERATURE RISE”

    under START--UP, ADJUSTMENT, and SAFETY

    CHECK.

    CAUTION

    !

    NOTE: Refer to Table 11 for motor speed lead relocation if

    leads were not identified before disconnection.

    17. Reconnect blower leads to furnace control. Refer to

    furnace wiring diagram, and connect thermostat leads if

    previously disconnected.

    18. To check blower for proper rotation:

    a. Turn on electrical supply.

    ELECTRICAL SHOCK HAZARD

    Failure to follow this warning could result in personal

    injury, or death.

    Blower access door switch opens 115-- v power to

    furnace control. No component operation can occur

    unless switch is closed. Exercise caution to avoid

    electrical shock from exposed electrical components

    when manually closing this switch for service purposes.

    !

    WARNING

    b. Manually close blower access door switch.

    NOTE: If thermostat terminals are jumpered at the time blower

    access door switch is closed, blower will run for 90 sec before

    beginning a heating or cooling cycle.

    c. Perform component self--test as shown at the bottom of

    the SERVICE label, located on the front of blower access

    door.

    d. Verify blower is rotating in the correct direction.

    19. If furnace is operating properly, RELEASE BLOWER

    ACCESS DOOR SWITCH. Remove any jumpers or

    reconnect any disconnected thermostat leads. Replace

    blower access door.

    20. Downflow or horizontal furnaces with vent pipe through

    furnace only:

    a. Install and connect short piece of vent pipe inside furnace

    to existing vent.

    b. Connect vent connector to vent elbow.

    21. Reinstall casing door.

    22. Turn on gas supply and cycle furnace through one

    complete heating and cooling cycle. Verify the furnace

    temperature rise as shown in “Adjustments” Section.

    Adjust temperature rise as shown in “Adjustments”

    Section. If outdoor temperature is below 70_F, (21_C)

    turn off circuit breaker to outdoor unit before running

    furnace in the cooling cycle. Turn outdoor circuit breaker

    on after completing cooling cycle.

    CLEANING HEAT

    EXCHANGER

    The following steps should be performed by a qualified

    service agency:

    NOTE: If the heat exchangers get a heavy accumulation of soot

    and carbon, they should be replaced rather than trying to clean

    313A

  • Page 48:

    48

    them thoroughly. A heavy build-- up of soot and carbon indicates

    that a problem exists which needs to be corrected, such as

    improper adjustment of manifold pressure, insufficient or poor

    quality combustion air, incorrect size or damaged manifold

    orifice( s), improper gas, or a restricted heat exchanger. Action

    must be taken to correct the problem.

    If it becomes necessary to clean the heat exchangers because of

    dust or corrosion, proceed as follows:

    1. Turn OFF gas and electrical power to furnace.

    2. Remove outer access door.

    3. Disconnect vent connector from furnace vent elbow.

    4. For downflow or horizontal furnace having an internal

    vent pipe, remove internal vent pipe within the casing.

    5. Disconnect wires to the following components. Mark

    wires to aid in reconnection of (be careful when

    disconnecting wires from switches because damage may

    occur):

    a. Draft safeguard switch.

    b. Inducer motor.

    c. Pressure switch(es).

    d. Limit overtemperature switch.

    e. Gas valve.

    f. Hot surface igniter.

    g. Flame--sensing electrode.

    h. Flame rollout switches.

    6. Remove screws that fasten the collector box assembly to

    the cell panel. Be careful not to damage the collector box.

    Inducer assembly and elbow need not be removed from

    collector box.

    7. Disconnect gas line from gas manifold.

    8. Remove the 5 screws that attach the burner assembly to

    the cell panel. The gas valve and individual burners need

    not be removed from support assembly. Remove NOx

    baffles if installed.

    NOTE: Be very careful when removing burner assembly to

    avoid breaking igniter. See Fig. 56 and 57 for correct igniter

    location.

    9. Using field--provided 25--caliber rifle cleaning brush,

    36 -- in. (914 mm) long, 1/4” (6 mm) diameter steel spring

    cable, a variable speed, reversible electric drill, and

    vacuum cleaner, clean cells as follows:

    a. Remove metal screw fitting from wire brush to allow

    insertion into cable.

    b. Insert the twisted wire end of brush into end of spring

    cable, and crimp tight with crimping tool or crimp by

    striking with ball--peen hammer. TIGHTNESS IS VERY

    IMPORTANT.

    9/32”

    7.1mm

    5/16”

    7.9mm

    A05025

    Fig. 56 -- Igniter Position--Side View

    1-7/8

    47.6 mm

    A05026

    Fig. 57 -- Igniter Position-- Top View

    NOTE: The materials needed in item 9 can usually be purchased

    at local hardware stores.

    (1.) Attach variable--speed, reversible drill to the end of

    spring cable (end opposite brush).

    (2.) Insert brush end of cable into the outlet opening of

    cell and slowly rotate with drill. DO NOT force

    cable. Gradually insert cable into upper pass of cell.

    (See Fig. 58.)

    (3.) Work cable in and out of cell 3 or 4 times to obtain

    sufficient cleaning. DO NOT pull cable with great

    force. Reverse drill and gradually work cable out.

    (4.) Insert brush end of cable in burner inlet opening of

    cell, and proceed to clean 2 lower passes of cell in

    same manner as upper pass.

    (5.) Repeat foregoing procedures until each cell in

    furnace has been cleaned.

    (6.) Using vacuum cleaner, remove residue from each

    cell.

    (7.) Using vacuum cleaner with soft brush attachment,

    clean burner assembly .

    (8.) Clean flame sensor with fine steel wool.

    (9.) Install NOx baffles (if removed).

    (10.) Reinstall burner assembly. Center burners in cell

    openings.

    10. Remove old sealant from cell panel and collector box

    flange.

    11. Spray releasing agent on the heat exchanger cell panel

    where collector box assembly contacts cell panel.

    NOTE: A releasing agent such as cooking spray or equivalent

    (must not contain corn or canola oil, aromatic or halogenated

    313A

  • Page 49:

    49

    hydrocarbons or inadequate seal may occur) and RTV sealant

    (G.E. 162, 6702, or Dow --Corning 738) are needed before

    starting installation. DO NOT substitute any other type of RTV

    sealant. G.E. 162 (P771--9003) is available through RCD in 3 --oz.

    tubes.

    12. Apply new sealant to flange of collector box and a ttach to

    cell panel using existing screws, making sure all screws

    are secure.

    13. Reconnect wires to the following components. (Use

    connection diagram on wiring label, if wires were not

    marked for reconnection locations.):

    a. Draft safeguard switch.

    b. Inducer motor.

    c. Pressure switch(es).

    d. Limit over--temperature switch.

    e. Gas valve.

    f. Hot surface igniter.

    g. Flame--sensing electrode.

    h. Flame rollout switches.

    i. Install NOx baffles (if removed).

    14. Reinstall internal vent pipe, if applicable.

    A91252

    Fig. 58 -- Cleaning Heat Exchanger Cell

    15. Reinstall vent connector on furnace vent elbow. Securely

    fasten vent connector to vent elbow with 2 field-- supplied,

    corrosion--resistant, sheet metal screws located 180_ apart.

    16. Replace blower access door only, if it was removed.

    17. Set thermostat above room temperature and check furnace

    for proper operation.

    18. Verify blower airflow and speed changes between heating

    and cooling.

    19. Check for gas leaks.

    20. Replace outer access door.

    FIRE OR EXPLOSION HAZARD

    Failure to follow this warning could result in personal injury,

    death and/or property damage.

    Never purge a gas line into a combustion chamber. Never

    test for gas leaks with an open flame. Use a commercially

    available soap solution made specifically for the detection of

    leaks to check all connections.

    !

    WARNING

    Sequence of Operation

    NOTE: Furnace control must be grounded for proper operation

    or control will lock out. Control is grounded through

    green/yellow wire routed to gas valve and manifold bracket

    screw. Using the schematic diagram in Fig. 59, follow the

    sequence of operation through the different modes. Read and

    follow the wiring diagram very carefully.

    NOTE: If a power interruption occurs during a call for heat (W),

    the control will start a 90--second blower--only ON period two

    seconds after power is restored, if the thermostat is still calling for

    gas heating. The Amber LED light will flash code 12 during the

    90 --second period, after which the LED will be ON continuous,

    as long as no faults are detected. After the 90--second period, the

    furnace will respond to the thermostat normally.

    The blower door must be installed for power to be conducted

    through the blower door interlock switch ILK to the furnace

    control CPU, transformer TRAN, inducer motor IDM, blower

    motor BLWM, hot--surface igniter HSI, and gas valve GV.

    1. Heating

    (See Fig. 25 for thermostat connections.)

    The wall thermostat “calls for heat,” closing the R--to--W

    circuit. The furnace control performs a self--check, verifies

    the pressure switch contacts PRS are open, and starts the

    inducer motor IDM.

    a. Inducer Pr epurge Period-- As the inducer motor IDM

    comes up to speed, the pressure switch contacts PRS close

    to begin a 15 --second prepurge period.

    b. Igniter Warm--Up-- At the end of the prepurge period,

    the Hot--Surface igniter HSI is ener gized for a 17--second

    igniter warm--up period.

    c. Trial--for-- Ignition Sequence-- When the igniter

    warm--up period is completed, the main gas valve relay

    contacts GVR close to energize the gas valve GV, the gas

    valve opens, and 24 vac power is supplied for a

    field--installed humidifier at the HUM terminal. The gas

    valve GV permits gas flow to the burners where it is

    ignited by the HSI. Five seconds after the GVR closes,

    a 2--second flame proving period begins. The HSI igniter

    will remain ener gized until the flame is sensed or until the

    2 -- second flame proving period begins.

    d. Flame--Proving-- When theburner flame is proved atthe

    flame--proving sensor electrode FSE, the furnace control

    CPU begins the blower--ON delay period and continues

    to hold the gas valve GV open. If the burner flame is not

    proved within two seconds, the control CPU will close

    the gas valve GV, and the control CPU will repeat the

    ignition s equence for up to three more

    Trials--For--Ignition before going to Ignition--Lockout.

    Lockout will be reset automatically after three hours or

    by momentarily interrupting 115 vac power to the

    furnace, or by interrupting 24 vac power at SEC1 or

    SEC2 to the furnace control CPU (not at W, G, R, etc.).

    If flame is proved when flame should not be present, the

    furnace control CPU will lock out of Gas--Heating mode

    and operate the inducer motor IDM until flame is no

    longer proved.

    e. Blower--On Delay-- If the burner flame is proven, the

    blower motor is energized on HEAT speed 25 seconds

    after the gas valve GV is energized.

    Simultaneously, the electronic air cleaner terminal

    EAC--1 is energized and remains energized as long as the

    blower motor BLWM is energized.

    f. Blower--Off Delay-- When the thermostat is satisfied, the

    R--to--W circuit is opened, de--energizing the gas valve

    GV, stopping gas flow to the burners, and de--energizing

    the humidifier terminal HUM. The inducer motor IDM

    will remain energized for a 5 --second post-- purge period.

    The blower motor BLWM and air cleaner terminal

    EAC--1 will remain energized for 90, 120, 150, or 180

    seconds (depending on the blower-- OFF delay selection).

    The furnace control CPU is factory-- setfor a 120 --second

    blower--OFF delay .

    313A

  • Page 50:

    50

    2. Cooling Mode

    The thermostat “calls for cooling.”

    a. Single-- Speed Cooling

    (See Fig. 25 -- 32 for thermostat connections)

    The thermostat closes the R--to--G --and--Y circuits. The

    R--to-- Y circuit starts the outdoor unit, and the

    R--to--G--and--Y/Y2 circuits start the furnace blower

    motor BLWM on COOL speed .

    The electronic air cleaner terminal EAC--1 is energized

    with 115 vac when the blower motor BLWM is operating.

    When the thermostat is satisfied, the R--to--G--and--Y

    circuits are opened. The outdoor unit will stop, and the

    furnace blower motor BLWM will continue operating on

    the COOL speed for an additional 90 seconds. Jumper

    Y/Y2 to DHUM to reduce the cooling off-- delay to 5

    seconds. (See Fig. 24.)

    b. Two--Speed Cooling

    (See Fig. 25 -- 32 for thermostat connections.)

    The thermostat closes the R--to--G--and--Y1 circuits for

    low--cooling or closes the R--to--G--and--Y1--and--Y2

    circuits for high--cooling. The R--to--Y1 circuit starts the

    outdoor unit on low--cooling speed, and the

    R--to--G--and--Y1 circuit starts the furnace blower motor

    BLWM on low--cool speed (same speed as FAN). The

    R--to--Y1 --and--Y2 circuits start the outdoor unit on

    high-- cooling speed, and the R -- to --Gand-- Y/Y2 circuits

    start the furnace blower motor BLWM on COOL speed.

    The electronic air cleaner terminal EAC--1 is energized

    with 115 vac whenever the blower motor BLWM is

    operating.

    When the thermostat is satisfied, the R--to--G--and--Y1 or

    R--to--G --and--Y1 and Y2 circuits are opened. The

    outdoor unit stops, and the furnace blower BLWM and

    electronic air cleaner terminal EAC--1 will remain

    energized for an additional 90 seconds. Jumper Y1 to

    DHUM to reducethecooling off-- delay to 5 seconds.(See

    Fig. 24.)

    3. Thermidistat Mode

    (See Fig. 26 --29 for Thermidistat connections.)

    The dehumidification output, DHUM o n the T hermid istat

    should be connected to the furnace control thermostat

    terminal DHUM. When there is a dehumidify demand, the

    DHUM input is activated, which means 24 vac signal is

    removed from the DHUM input terminal. In other words,

    the DHUM input logic is reversed. The DHUM input is

    turned ON when no dehumidify demand exists. Once 24

    vac is detected by the furnace control on the DHUM input,

    the furnace control operates in Thermidistat mode. If the

    DHUM input is low for more than 48 hours, the furnace

    control reverts back to non--Thermidistat mode.

    The cooling operation described in item 2. above also

    applies to operation with a Thermidistat. The exceptions

    are listed below:

    a. When the R--to--G--and--Y1 circuit is closed and there is

    a demand fordehumidification, thefurnace blowermotor

    BLWM will continue running at low--cool speed (same

    speed as F AN).

    b. When the R-- to --G --and-- Y/Y2 circuit is closed and there

    is a demand for dehumidification, the furnace blower

    motor BLWM will drop the blower speed from COOL

    to HEAT for a maximum of 10 minutes before reverting

    back to COOL speed. If there is still a demand for

    dehumidification after 20 minutes, the furnace control

    CPU will drop the blower speed back to HEAT speed.

    This alternating 10-- minute cycle will continue as long

    as there is a call for cooling.

    c. When the “call for cooling” is satisfied and there is a

    demand for dehumidification, the cooling blower--of f

    delay is decreased from 90 seconds to 5 seconds.

    4. Continuous Blower Mode

    When the R--to--G circuit is closed by the thermostat, the

    blower motor BLWM will operate on continuous-- blower

    speed (can be adjusted to FAN, HEAT, or COOL speed) at

    the thermostat. Factory default is FAN speed. Terminal

    EAC--1 is energized as long as the blower motor BLWM is

    energized. During a call for heat, the blower BLWM will

    stop during igniter warm-- up (17 seconds), ignition (7

    seconds), and blower-- ON delay (25 seconds), allowing

    the furnace heat exchangers to heat up more quickly, then

    restarts at the end of the blower--ON delay period at HEAT

    speed.

    In heating, the furnace control CPU will hold the blower

    motor BLWM at HEAT speed during the selected

    blower--OFF delay period before reverting to

    continuous--blower speed. When the thermostat “calls for

    low--cooling,” the blower motor BLWM will switch to

    operate at low--cool speed (same speed as F AN). When the

    thermostat is satisfied, the blower motor BLWM will

    operate an additional 90 seconds on low-- cool speed (same

    speed as FAN) before reverting back to

    continuous--blower speed.

    When the thermostat “calls for high-- cooling”, the blower

    motor BLWM will operate at COOL speed. When the

    thermostat is satisfied, the blower motor BLWM will

    operate an additional 90 seconds on COOL speed before

    reverting back to continuous--blower speed.

    When the R--to--G circuit is opened, the blower motor

    BLWM will continue operating for an additional 5

    seconds, if no other function requires blower motor

    BLWM operation.

    Continuous Blower Speed Selection from Thermostat

    -- To select different continuous--blower speeds from the

    room thermostat, momentarily turn off the FAN switch or

    pushbutton on the room thermostat for 1 --3 seconds after

    the blower motor BLWM is operating. The furnace control

    CPU will shift the continuous-- blower speed from the

    factory setting of FAN to HEAT speed. Momentarily

    turning of f the FAN switch again at the thermostat will

    shift the continuous-- blower speed from HEAT to COOL.

    Repeating the procedure will shift the continuous--blower

    speed from COOL to FAN speed. The selection can be

    changed as many times as desired and is stored in the

    memory to be automatically used following a power

    interruption.

    313A

  • Page 51:

    51

    5. Heat pump

    (See Fig. 25 -- 32 for thermostat connections.) When

    installed with a heat pump, the furnace control

    automatically changes the timing sequence to avoid long

    blower off times during demand defrost cycles. When the

    R -- t o -- W -- a n d -- Y 1 o r R -- t o -- W -- a n d -- Y 1 -- a n d -- G c i r c u i t s

    are energized the furnace control CPU will switch to or

    turn on the blower motor BLWM at HEAT speed, and

    begin a heating cycle. The blower motor BLWM will

    remain on until the end of the prepurge period, then shut

    off for 24 seconds then come back on at HEAT speed.

    When the W input signal disappears, the furnace control

    begins a normal inducer post--purge period and the blower

    remains running at HEAT speed for the selected

    blower--OFF delay period then switches to low--cool

    speed (same speed as FAN). If the

    R--to--W --and-- Y1-- and--G signals disappear at the same

    time, the blower motor BLWM will remain on for the

    selected blower--OFF delay period. If the R--to--

    W--and-- Y1 signals disappear, leaving the G signal, the

    blower motor BLWM will remain on for the selected

    blower--OFF delay period then switch to

    continuous--blower speed. When the R --to-- W-- and--Y/Y2,

    R--to--W--and--Y/Y2--and--G, R--to--W--and--Y1--and--

    Y / Y 2 , o r R -- t o -- W -- a n d -- Y 1 -- a n d -- Y / Y 2 -- a n d -- G c i r c u i t s

    are energized the furnace control CPU will switch to or

    turn on the blower motor BLWM at HEAT speed, and

    begin a heating cycle. The blower motor BLWM will

    remain on until the end of the prepurge period, then shut

    off for 24 seconds then come back on at HEAT speed.

    When theWinput signal disappears, the furnace control

    begins a normal inducer post--purge period and the blower

    switches to COOL speed after a 3 second delay. If the

    R -- t o -- W -- a n d -- Y / Y 2 -- a n d -- G o r R -- t o -- W -- a n d -- Y 1 -- a n d --

    Y/Y2--and--G signals disappear at the same time, the

    blower motor BLWM will remain on for the selected

    blower--OFF delay period. If the R-- to--W --and--Y/Y2 or

    R--to--W --and-- Y1-- and--Y/Y2 signals disappear, leaving

    the G signal, the blower motor BLWM will remain on for

    the selected blower--OFF delay period then switch to

    continuous blower speed.

    Wiring

    Diagrams

    Refer to Fig. 59 for wiring diagram.

    Tr

    oubleshooting

    Refer to the service label. (See Fig. 55.) The Troubleshooting

    Guide (See Fig. 60) can be a useful tool in isolating furnace

    operation problems. Beginning with the word “Start,” answer

    each question and follow the appropriate arrow to the next item.

    The Guide will help to identify the problem or failed component.

    After replacing any component, verify correct operation

    sequence.

    313A

  • Page 52:

    52

    A08176

    Fig. 59 -- Wiring Diagram

    313A

  • Page 53:

    53

    Is LED status light on?

    Is LED status light blinking rapidly without a

    pause?

    Is LED status light blinking ON/OFF slowly

    with a combination of short and long

    flashes?

    Determine status code. The status code is a

    2 digit number with the first digit determined

    by the number of short flashes and the second

    digit by the number of long flashes?

    Go to section below for the status code that

    was flashed.

    Is there 115V at L1 and L2?

    Is there 24V at SEC-1 and SEC-2?

    Replace furnace control.

    Check for correct line voltage polarity. If units

    are twinned, chec

    k for proper low-voltage

    (24V) transformer phasing.

    To

    recall status code briefly remove and reconnect one RED wire from the draft

    safeguard switch to display stored status code. On RED LED control do not

    remove power or blower access panel before initiating status code recall. You

    can also recall the previous

    status

    code by momentarily

    shorting the TEST/TWIN

    terminal to Com24V terminal until the LED goes out. LED will flash the status

    code of the previous fa

    ult or status code #11 (1 shor

    t and 1 long flash) if there

    was no previous fault. After the control repeats the code 4 times, the control

    will go through a brief component test sequence. The

    inducer will star

    t and run

    for the entire component test. The HSI, blower motor FAN speed (AMBER LED

    boards only) HEAT speed, and COOL speed will run for 10 – 15 seconds each.

    Gas valve and humi

    difier will not be turned on.

    Was there a previous status code

    other than #11?

    Is door switch closed?

    Is there 115V going to switch?

    Replace door switch.

    Replace transformer.

    Does the control respond to W, Y1 (if present),

    Y/Y2, and G (24V) thermostat signals?

    Run system through a heating or cooling cycle

    to check operation. Status codes are erased

    after 72 hours.

    On RED LED boards stored

    status codes can also be erased whenever

    (115V or 24V) is interrupted.

    Replace furnace control.

    Is door switch closed?

    Is circuit breaker closed?

    Check for continuity in wire from c

    ircuit breaker

    to furnace.

    Close circuit break

    er and go back to START.

    Check room thermostat or

    interconnecting cable.

    Is 24V present at W, Y1 (if present), Y/Y2 or

    G thermostat terminals on the furnace control?

    Disconnect all the thermostat wires from the

    furnace control.

    Does the problem repeat when using

    a jumper wire?

    The thermostat is not compatible with the

    furnace

    control.

    Either install a ballast resistor,

    connect the Com24V thermostat terminal to

    the thermostat, or replace the thermostat.

    NO

    YES

    YES

    NO

    NO

    YES

    YES

    YES

    YES

    NO

    YES

    YES

    NO

    YES

    NO

    YES

    NO

    NO

    NO

    YES

    NO

    YES

    NO

    START

    NO

    A02106A

    Fig. 60 -- Troubleshooting Guide

    313A

  • Page 54:

    54

    11 NO PREVIOUS CODE – Stored codes

    are erased after 72 hours. On RED LED

    boards stored status codes can also be

    erased whenever power (115V or 24V)

    is interrupted. Run system through a

    heating or cooling cycle to check system.

    12 BLO

    WER ON AFTER POWER UP –

    (115V OR 24V) – Normal operation.

    Blower runs for 90 seconds, if unit is

    powered up during a call for heat (R-W

    closed) or when (R-W opens) during the

    blower on-delay period.

    13LIMIT CIRCUIT LOCKOUT – Lockout

    occurs if the limit, draft safeguard, flame

    rollout, or blocked vent sw

    itch*(if used) is

    open longer than 3 minutes. Control will

    auto-reset after 3 hours. See code 33.

    14 IGNITION LOCKOUT – System failed to

    ignite gas and prove flame in 4 attempts.

    Control will auto-reset after 3 hours.

    See status code 34.

    21 GAS HEATING LOCKOUT – Turn off

    power and wait 5 minutes to retry.

    Check for:

    - Stuck closed gas valve relay on control.

    - Miswire or short to gas valve wire.

    22 ABNORMAL

    FLAME-PROVING SIGNAL

    Flame is proved wh

    ile gas valve is de-

    energized. Inducer will run until fault is

    cleared. Check for:

    - Stuck open or leaky gas valve.

    23 PRESSURE SWITCH DID NOT OPEN

    Check for:

    - Obstructed pressure tube.

    - Pressure switch stuck closed.

    24SECONDARY VO

    LTA

    GE FUSE IS OPEN

    Check for:

    -Short circuit in

    secondary voltage (24V)

    wiring including thermostat leads.

    Disconnect thermostat leads to

    isolate

    short ci rcuit.

    31 PRESSURE SWITCH DID NOT CLOSE

    OR REOPENED – If open longer than 5

    minutes, inducer shuts off for 15 minutes

    before retry. If opens during blower on-

    delay period, blower will come on for the

    selected blower off-delay. Check for:

    - Proper vent sizing.

    -Low inducer voltage (115V).

    -Low inlet gas pressure (if LGPS used).

    -Inadequate combustion air supply.

    -D

    isconnected or obstructed pressure

    tubing.

    - Defective inducer motor.

    - Defective pressure switch.

    -Excessive win

    d.

    -Restricted v

    ent.

    33 LIMIT CIRCUIT FAULT – Indicates the

    limit, draft saf

    eguard, flame rollout, or

    blocked vent shutoff switch* (if used) is

    open. Blower will run for 4 minutes or

    until open switch remak

    es whichever

    is

    longer. If ope

    n longer than 3 minutes,

    code changes to lockout #

    13. If open

    less than 3 min.

    status code #33

    continues to flash until blower shuts off.

    Flame

    rollout sw

    itch and BVSS requires

    manual reset. Check for:

    -Dirty filter or restricted duct system.

    -

    Loose blower wheel.

    - Defective switch or connections.

    - Defective blower motor or capacitor.

    -Inadequate combustion air supply

    (flame rollout switch open).

    - Restricted vent.

    - Proper vent sizing.

    -E

    xcessive wind.

    34 IGNITION

    PR

    OVING FAILURE – If flame

    is not sensed during the trial for ignition

    period, the control will repeat the ignition

    sequence 3 more times before lockout

    #14 occurs. If flame signal is lost during

    the blower on-delay period, blower will

    come on for the selected bl

    ower off-del

    ay.

    Check the following items first before

    proceeding to the next step.

    -Gas valve turned off.

    - Manual shut-off v

    alve.

    -Green/Ye l l o w wire MUST be connected

    to furnace sheet metal.

    - F

    lame sensor must not be grounded.

    To determine whether the problem is in

    the gas

    valve, igniter

    , or flame sensor the

    system can be operated in

    the component

    test mode to check the igniter. First

    remove the R thermostat connection from

    the control and initiate the component

    test sequence. Does the igniter gl

    ow

    orange

    /white by the end

    of the 15 second

    wa

    rm

    -up period?

    Unplug igniter har

    ness from control and initiate

    another component test sequence. Check

    for 115V between pin 1 and NEUTRAL-L2 on

    the control. Was 115V present for the 15

    second period?

    Reconnect the R thermostat lead and set

    thermostat to c

    all for heat. Connect voltmeter

    across gas va

    l

    ve

    connections. Does gas va

    lve

    receive 24V?

    Does gas valve open and allow gas to flow?

    Do the main burners ignite?

    Do the main burners stay on?

    Repeat call for heat and check flame sensor

    current during trial for ignition period. Is the

    DC microamps below 0.5?

    Is current near typical v

    alue?

    Will main burners ignite and stay on?

    Fixed.

    Clean flame sensor with fine steel wool and

    recheck current. Nominal current is 4.0 to 6.0

    microamps.

    45CONTROL CIRCUITRY LOCKOUT

    Auto-reset after 1 hour lockout due to:

    - Flame circuit failure.

    -Gas valve relay stuck open.

    - Software check error.

    Reset power to clear lockout. Replace

    control if code repeats.

    Replace furnace control.

    Check for continuity i

    n the harness

    and

    ignite

    r.

    Replace defectiv

    e component.

    Check connections. If OK, replace control

    .

    Check that all gas valves are turned on.

    Replace valve.

    Chec

    k for:

    -Inadequate flame carr

    yover or rough

    ignition.

    -Low inlet gas pressure.

    - Proper fir

    ing rate

    .

    - Blocked or incorrect carry- over gap.

    (.045” nominal)

    Allow blower to come on and repeat test to

    check for intermittent operation.

    Check connections and retry. If current is

    near typical value (4.0-6.0 nominal) and

    burners will not stay on, replace control.

    Replace electrode.

    Replace fur

    nace control.

    * Blocked vent shutoff switch used in Chimney Adapter Kit

    YES

    YES

    YES

    YES

    NO

    YES

    YES

    YES

    NO

    YES

    NO

    NO

    NO

    YES

    NO

    NO

    NO

    NO

    A05032

    Manufacturer reserves the ri ght to disc ontinue, or change at any time, specifications or designs without notice and without incurring obligations.

    E2008 Bryant Heating & Co ol ing Systems 7310 W. Mo rris St. Indianapolis, IN 46231 Printed in U.S.A. Edition Da te: 10/08

    Replaces: II313AAV---02

    Catalog No. II313AA

    V

    --- 0 3

    313A

Bryant 313AAV Furnace Installation, Start-up, Operating And Service And Maintenance Instructions | Guidessimo.com (2024)
Top Articles
Latest Posts
Article information

Author: Eusebia Nader

Last Updated:

Views: 6036

Rating: 5 / 5 (60 voted)

Reviews: 91% of readers found this page helpful

Author information

Name: Eusebia Nader

Birthday: 1994-11-11

Address: Apt. 721 977 Ebert Meadows, Jereville, GA 73618-6603

Phone: +2316203969400

Job: International Farming Consultant

Hobby: Reading, Photography, Shooting, Singing, Magic, Kayaking, Mushroom hunting

Introduction: My name is Eusebia Nader, I am a encouraging, brainy, lively, nice, famous, healthy, clever person who loves writing and wants to share my knowledge and understanding with you.